A Experimental Study on the Fire Hazard Analysis For Communication Cable in Buildings  

Hong, Sung-Ho (Fire Insurers Laboratories of Korea)
Choi, Moon-Soo (Fire Insurers Laboratories of Korea)
Publication Information
Journal of the Korean Society of Safety / v.26, no.6, 2011 , pp. 20-25 More about this Journal
Abstract
This study presents on the fire hazard analysis of communication cable in buildings. In order to analyze fire hazards for communication cable IEC 60332-1, UL 94 and cone calorimeter test are conducted. The number of cable used to experiment is 10 communication cable which are generally applied to data communication in buildings. The results show that 9 cables do meet the performance requirement of IEC 60332-1 and 8 cables are V-0 classification. IEC 60332-1 and UL 94 test are inadequate for fire hazard classification. The various parameters obtained by cone calorimeter test such as HRR, peak HRR, smoke production rate and so on. Also it is able to evaluate multiply fire hazard for communication cable with cone calorimeter test results.
Keywords
cable; fire hazard; fire classification; communication cable; cable fire;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 임혁순, 김두현, "원전 케이블 화재 열속평가 및 열화 진단방법에 관한 연구", 한국안전학회지, Vol. 26, No. 2, pp. 20-25, 2011.
2 김성찬, 이성혁, "케이블 화재의 화염전파 해석을 위한 FDS 모델의 격자민감도 평가", 한국안전학회지, Vol. 23, No. 4, pp. 30-35, 2008.
3 박양범, 한상옥, "케이블화재 방재대책", 한국화재소방학회논문지, Vol. 9, No. 2, pp.47-56, 1995.
4 P. Andersson, L. Rosell, M. Simonson, and V. Emanuelsson, "Small and Large Scale Fire Experiments with Electric Cables under Well-Ventilated and Vitiated Conditions", Fire Technology Vol. 40, No. 3, pp. 247-262, 2004.   DOI
5 IEC 60332-1, Test on Electric Cables Under Fire Conditions, 2002.
6 UL 94, Test for Flammability of Plastic Materials for Parts in Devices and Appliances, 2000.
7 ISO 5660-1, Reaction-to-fire tests, Heat release, smoke production and mass loss rate-Part 1: Heat release rate(cone calorimeter method), 2002.
8 ASTM E 1354, Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter, 2004.