Browse > Article

A Study on Ignition Hazard Caused by Electrostatic Discharge of Gasoline Used in the Gas Station  

Moon, Kyoon-Tae (The Graduate School of Energy and Environment, Seoul National University of Technology)
Chung, Jae-Hee (The Graduate School of Energy and Environment, Seoul National University of Technology)
Mizuki, Yamaguma (Japan National Institute of Occupational Safety and Health)
Choi, Kwang-Seok (Yamaguma Japan National Institute of Occupational Safety and Health)
Publication Information
Journal of the Korean Society of Safety / v.25, no.4, 2010 , pp. 13-18 More about this Journal
Abstract
To investigate electrostatic ignition hazards of commercial gasoline used in the gas station, experiments were conducted dealing with the minimum ignition energy(MIE) of several kinds of gasoline under the various temperature. The conductivity of gasoline that was required for an accurate risk assessment as well as the MIE were also examined. The solvent ignitability apparatus which can heat up the inside of the vessels up to $210^{\circ}C$ was used in this study. Four kinds of premium gasoline and four kinds of regular gasoline, differing with respect to the companies, were used as test specimens. The following results were obtained: (1) all gasoline specimens were so sensitive that even an electrostatic discharge with a very low energy, such as about 0.5mJ, could ignite them. The ignitability of premium gasoline was constant irrespective of the companies. On the other hand, the ignitability of regular gasoline was variable depending on the company. (2) The MIE of all specimens depended markedly on the temperature; in other words, an increase in temperature decreases the ignition energy value. (3) The conductivity values of all specimens were low. Those must be taken into consideration in electrostatic risk assessment.
Keywords
electrostatic discharge; minimum ignition energy; gasoline; fire.explosion; gas station;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 김진걸, 최영록,"자동차정비교본", pp. 110, 2008.
2 이금환, 정재희, "가스충전소에서 작업복와 정전기 안전관리에 관한 연구", 한국안전학회지, 제24권, 제6호, pp. 39-44, 2009.   과학기술학회마을
3 이덕출, 정재희, "산업전방에 걸친 정전기재해와 장해방지", 성안당, pp. 6-7, 1996.
4 김두현외 4 명, "정전기 안전", 신광문화사, pp. 46-47, 2001.
5 임성묵외 4 명, "자동차 엔진 화재용 자동 소화 시스템 개발에 관한 연구" 한국소방학회 학술발표회, pp. 57-61, 1996.
6 한국주유소협회. http://www.ikosa.or.kr
7 소방방재청, http://www.nema.go.kr
8 한국산업 안전보건공단, http://www.kosha.or.kr
9 한국석유관리원, http://www.kipeq.or.kr
10 Measurement of ignition energies and explosion limits for organic solvent vapors, featuring temperature characteristics, 安全工學,Vol. 47, No. 2, pp 84-91, 2008.
11 산업자원부 기술표준원, "정전기 안전 실무 지침", pp. 165-168, 2003.