Browse > Article

Assessment of Possibility on the Human Risk for the Electromagnetic Field of Unbalanced Two Coupled Three-phase Transmission Line Using Fuzzy Theory  

Kim, Sang-Chul (Department of Safety Engineering, Semyung University)
Kim, Doo-Hyun (Department of Safety Engineering, Chungbuk University)
Publication Information
Journal of the Korean Society of Safety / v.21, no.2, 2006 , pp. 22-28 More about this Journal
Abstract
This paper presents assessment of possibility on the human risk for the electromagnetic field of unbalanced two coupled three-phase transmission line using fuzzy theory. Three phase load flow program was developed which employed a Newton-Raphson method as a tool to analyze system unbalanced. This research presents a method of handling two coupled three phase transmission system unbalance analysis and unbalanced power demand as a function of voltages. As the results of case study, in case of 345[kV] T/L, the electric field intensity was 10.9540[kV/m], magnetic field intensity was 0.2567[G] in severest case. The results showed that the membership of a proposition fuzzy '10.9540 [kV/m] is hazardous' is 0.6349. As the analytic results using the fuzzy qualifier term, the membership in case of very false is 0.1379 and fairly false is 0.6124, respectively. In assessment of fuzzy measure possibility for the electromagnetic field, this paper used probability of fuzzy arid measure of fuzziness technique.
Keywords
human risk; fuzzy qualifier term; fuzzy measure possibility; fuzziness technique;
Citations & Related Records
연도 인용수 순위
  • Reference
1 J. Arrillaga and c. p. Arnold, 'Computer Modellind of Electrical power systems', John Wiley son, 1983
2 Klir, G. J., and Folger, T. A., 'Fuzzy Sets, Uncertainty, and Information', Prentice Hall: New Jersey, 1988
3 Fan Zhang, Carol s. Cheng, 'A Modified Newton Method for Radial Distribution System Power Flow Analysis', IEEE Trans. on power systems, Vol. 12, No. I, pp. 389-397, February, 1997   DOI   ScienceOn
4 이광형 외 1, '퍼지이론 및 응용 I', 홍릉과학출판사, 1992
5 R. G. Wasiey and M. A. Shlash, ''Newton Raphson Algorithm for 3-phase Load Flow', proc. lEE, Vol. 121, No.7, pp. 630-638, July, 1974
6 송현선, '3상 조류계산에 의한 대규모 배전계통의 불평형상태 평가', 한국조명.전기설비학회지, 제13권, 제1호, pp. 86-93, 1999
7 김상철 외 2, '불평형계통에서의 전자계에 대한 인체안전평가', 한국산업안전학회지, 제14권, 제3호, pp. 54-62, 1999
8 김상철 외 2, '계통상태를 고려한 ELF 전자계의 인체안전평가를 위한 퍼지언어 변수 접근법', 한국산업안전학회지, 제12권, 제2호, pp. 70-79, 1997
9 WHO, 'Environmental Health Criteria 35', 1984