Browse > Article

Measurement and Analysis of Surges on Information Devices Installed in a Power Substation  

Song Jae-yong (한국해양대학교 전기전자공학부)
Park Dae-won (한국해양대학교 전기전자공학부)
Seo Hwang-dong (한국해양대학교 전기전자공학부)
Han Joo-sup (한국해양대학교 전기전자공학부)
Kil Gyung-suk (한국해양대학교 전기전자공학부)
Abstract
This paper deals with the analysis results of surge voltage and current measured on information devices installed in a power substation. The power recorder to measure surge voltage and current was connected to signal lines near power transformers and switches, and the time resolution of the power recorder is 4 MS/s. Peak value of the measured surge voltage and current were ranges of 500~1,300v and 500~3,100k, respectively. During the period of measurement, over 5~10 events per day were recorded. Consequently, information devices installed in around high voltage power facilities should be designed considering the surge voltage and current caused in the condition.
Keywords
surge voltage; surge current; information devices; power recorder; power transformer;
Citations & Related Records
연도 인용수 순위
  • Reference
1 길경석, '정보통신기기용 과도이상전압의 고 속도 차단장치의 설계 및 제작', 대한전기학회 논문지, Vol. 48, No.1, pp .51-56, 1999
2 IEEE C62.41 IEEE Recommended Protective on Surge voltages in Low-voltage AC Power Circuit, 1991
3 S. B. Smith and R. B. StaSndler, 'The Effects of Surges on Electric Appliances', IEEE Trans. on Power Delivery, vol. 7, pp. 127 5-1282, 1992
4 IEC 61000-4-5, Surge immunity test, pp. 6 0-77, 1999
5 KS C 0266, 산업용 설비에서의 전자파 적합성에 관한 기술지침, 1998
6 Bachman, L. Gullberg, F. Stricker, and H. Sachs,' An Assessment of shipboard Power Line Transients', IEEE International Symposium on Electromagnetic Compatibility, pp. 218-223, 1981