Abstract
Assessing the energy performance of supertall buildings often does not consider variations in energy consumption due to the change of environmental conditions such as temperature, pressure, and wind speed associated with differing elevations. Some modelers account for these changing conditions by using a conventional temperature lapse rate, but not many studies confirm to the appropriateness of applying it to tall buildings. This paper presents and discusses simulated annual energy consumption results from a 600 m tall skyscraper floor plate located in Dubai, UAE, assessed using ground level weather data, a conventional temperature lapse rate of $6.5^{\circ}C/km$, and more accurate simulated 600 m weather data. A typical office floorplate, with ASHRAE 90.1-2010 standards and systems applied, was evaluated using the EnergyPlus engine through the OpenStudio graphical user interface. The results presented in this paper indicate that by using ground level weather data, energy consumption at the top of the building can be overestimated by upwards of 4%. Furthermore, by only using a lapse rate, heating energy is overestimated by up to 96% due to local weather phenomenon such as temperature inversion, which can only be conveyed using simulated weather data. In addition, sizing and energy consumption of fans, which are dependent both on wind and atmospheric pressure, are not accurately captured using a temperature lapse rate. These results show that that it is important, with the ever increasing construction of supertall buildings, to be able to account for variations in climatic conditions along the height of the building. Adequately modeling these conditions using simulated weather data will help designers and engineers correctly size mechanical systems, potentially decreasing overall building energy consumption, and ensuring that these systems are able to provide the necessary indoor conditions to maintain occupant comfort levels.
Keywords
Energy modeling; Microclimate; Simulated weather; Lapse rate; Supertall buildings;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Phillips, D. (2012 June). Meteorological Data in a Humid Climate at Grade and 1970ft /600m, ASHRAE Annual Conference, Houston, TX.
2 ASHRAE. (2005). Fundamentals Handbook 2005. ASHRAE, USA.
3 Leung, L., & Weismantle, P. (2008). How Supertall Buildings Can Benefit From Height. CTBUH 2008 8th World Congress, Dubai, CTBUH.
4 Ellis, P.G. & Torcellini, P.A. (2005). Simulating Tall Buildings Using Energy Plus, Ninth International Building Performance Simulation Association Conference and Exhibition, Montreal, IBPSA.
5 Saroglou, T., Meir, I.A., & Theodosiou, T. (2017). Quantifying Energy Consumption in Skyscrapers of Various Heights. Procedia Environmental Sciences, 38, pp. 314-321.   DOI
6 Lotfabadi, P. (2013). High-rise buildings and environmental factors. Renewable and Sustainable Energy Reviews, 38, pp. 285-295.   DOI