Abstract
This is a basic research on potential application of fire detection by measuring fire detection tendency of indoor air quality measurement factors. In this study, operation experiment using smoke detector sensitivity tester and paper fire experiment specified in UL 268 standards were conducted to evaluate the fire detection tendency of indoor air quality measurement factors. Based on the cross-substitution of values measured in the paper fire experiment, PM10 (excluding average) and HCHO (excluding average and maximum) for the indoor air quality meter (IAQ); PM1.0, PM2.5, and PM10 for IAQ S2; and CO (excluding the average and maximum) for combustion gas analyzers showed consistent tendency despite changes in the measured values for smoke generation under all experimental conditions. In particular, PM10 and CO are considered the most applicable fire detection factors among the factors measured in the experiment.
Keywords
Fire detection; IAQ measure factors; UL 268 paper fire; Fire detection tendency; Fire detection factor;
Citations & Related Records
연도 인용수 순위
  • Reference
1 National Fire Agency 119, "National Fire Information Center Fire Statistics" (2018).
2 NFSC 203, "Fire Safety Standards for Automatic Fire Alarm System and Visual Alarm Equipment" (2019).
3 C. H. Lee, H. S. Lee and S. K. Kim, "A Study on Response Characteristics of Photoelectric Type Smoke Detector Chamber Due to Dust and Wind Velocity", Fire Science and Engineering, Vol. 31, No. 1, pp. 50-57 (2017).   DOI
4 H. S. Lee and S. K. Kim, "A Study on Response Characteristics of Photoelectric Type Smoke Detector Chamber Due to Dust Color", Fire Science and Engineering, Vol. 31, No. 5, pp. 44-52 (2017).   DOI
5 H. Y. Jang and C. H. Hwang, "Revision of the Input Parameters for the Prediction Models of Smoke Detectors Based on the FDS", Fire Science and Engineering, Vol. 31, No. 2, pp. 44-51 (2017).   DOI
6 Ministry of Environment, "Indoor Air Quality Management Act" (2018).
7 Underwriters Laboratories, "UL 268 Standard for Safety Smoke Detectors for Fire Alarm Systems" (2016).
8 http://rm.samsungfire.com/pub/html/2002/2002wtr11.html.
9 Y. G. Park, "An Experimental Study on the Combustion Risk Characteristics of Industry Using Insulating Materials", Academy Thesis, The Graduate School of Hoseo University, pp. 36-37 (2005).
10 J. H. Lee, "A Study on the Multi-optical Smoke Detector Chamber", Ph.D. Thesis, The Graduate School of Hoseo University, pp. 1-118 (2013).
11 K. H. Kim and C. H. Hawng, "Measurement of the Device Properties of a Ionization Smoke Detector to Improve Predictive Performance of the Fire Modeling", Journal of Korean Institute of Fire Science & Engineering, Vol. 27, No. 4, pp. 27-34 (2013).
12 National Fire Agency 119 Notice (No. 2017-5), "Technical Standards for Formal Approval and Product Inspection of Fire Detector" (2019).