Evaluation of the Reaction-to-fire Performance of Pipe Insulation Material using Small Room Test  

Lim, Ohk Kun (R&D Laboratory, Korea Fire Institute)
Nam, Dong-gun (R&D Laboratory, Korea Fire Institute)
Jang, Hyo-Yeon (R&D Laboratory, Korea Fire Institute)
Publication Information
Fire Science and Engineering / v.33, no.4, 2019 , pp. 1-8 More about this Journal
Abstract
Reaction-to-fire performance of pipe insulation materials should be approved in accordance with KS standards prior to installing water-based suppression systems because several fire accidents are initiated from insulation materials around ceilings or concealed space. A small room test to evaluate the reaction-to-fire performance of the polyethylene foam and elastomeric pipe insulation materials was conducted according to ISO 20632. Different fire growth rate and heat release rate are observed depending on the materials and construction methods. In order to improve a fire safety, the reaction-to-fire performance of pipe insulation material needs to be subdivided with regard to the heat release rate and smoke generation. Furthermore, the characteristics of the applying space are also required to be considered. Subsidiary materials for installation process such as tape and adhesive are found to provide an adverse effect to maintain a fire safety.
Keywords
Pipe insulation; Reaction-to-fire performance; Fire safety; Room corner test; Concealed space;
Citations & Related Records
연도 인용수 순위
  • Reference
1 BS EN ISO 11925-2:2010, "Reaction to Fire Tests - Ignitability of Products Subjected to Direct Impingement of Flame Part 2: Single-flame Source Test", British Standard Institution (BSI), London, UK (2010).
2 ISO 20632, "Reaction-to-fire Tests - Small Room Test for Pipe Insulation Products or Systems", International Organization for Standardization (ISO), Switzerland (2008).
3 B. Sundstorm, P. Hees and P. Thureson, "Results and Analysis from Fire Tests of Building Products in ISO 9705, the Room/Corner Test", SP Report 1998:11, Swedish National Testing and Research Institute (1998).
4 Y. I. Kim, K. S. Chung, H. Oh, S. Suh, J. Oh and B. Park, "Research on Improvement of Insulation Construction Performance", Proceedings of 2009 Winter Annual Conference, The Society of Air-Conditioning and Refrigeration Engineers of Korea, pp. 336-341 (2009).
5 E. P. Lee, "Analysis of the Working Conditions of Screen Fire Shutters in the Goyang Bus Terminal Fire", Fire Science and Engineering, Vol. 32, No. 2, pp. 82-91 (2018).   DOI
6 O. K. Lim, D. Nam and J. Jeong, "Study on Reactionto-fire Performance of Pipe Insulation Materials", Proceedings of 2019 Spring Annual Conference, Korean Institute of Fire Science & Engineering, pp. 139-140 (2019).
7 C. K. Chang, Y. H. Yoo, H. S. Kim and J. O. Park, "An Experimental Study on a Fire Evaluation of the Interior Space of a Ceiling For Station", Journal of Korean Fire Investigation Society, Vol. 6, No. 3, pp. 1-12 (2015).
8 The International Code Council (ICC), "2018 The International Building Code", ICC, USA (2017).
9 Department for Communitites and Local Government (DCLG), "The Building Regulations 2010 Approved Document B: Fire Safety. Volume 2: Building Other than Dwelling Houses", UK (2013).
10 NFPA 101, "Life Safety Code", 2018 Ed., National Fire Protection Association (NFPA), USA (2018).
11 BS EN 13501-1:2007+A1:2009, "Fire Classification of Construction Products and Building Elements - Part 1: Classification Using Data from Reaction to Fire Tests", British Standard Institution (BSI), London, UK (2009).
12 D. H. Kim and B. Park, "The survey on the Insulation Status of Heating Pipes Installed in Apratment Complex", Proceedings of 2009 Winter Annual Conference, The Society of Air-Conditioning and Refrigeration Engineers of Korea, pp. 662-665 (2009).