Analysis of Causes of Casualties in Jecheon Sports Center Fire - Focus on Structural Factors of Building and Equipment -  

Lee, Eui-Pyeong (Dept. of Fire Safety Engineering, Jeonju University)
Publication Information
Fire Science and Engineering / v.32, no.4, 2018 , pp. 86-94 More about this Journal
Abstract
A sports center fire in Jecheon caused 29 deaths and 40 injuries. This study focused only on the structural factors of the building and equipment to investigate the causes of casualties based on the fire investigation results at the sports center. The structural factors of the building and equipment were a piloti-type parking lot, lack of a fire compartment between the piloti-type parking lot and lobby, lack of an installed sprinkler system, lack of an installed fire door in the main stairs on the $1^{st}$ floor, lack of an installed fire water tank on the rooftop, an installed pocket fire door in the main entrance on the $2^{nd}$ floor, poor fire compartments in an EPS space and a pipe pit and on each floor, a leak in the joint of a drain pipe, plywood installed in the hoistway of the freight elevator and interior wall, illegal remodeling of a closed rooftop structure, which cannot discharge smoke and heat, installed styrofoam insulation in the inside of the parking lot ceiling, an installed tempered glass window, which cannot be opened in the ladies bathroom on the $2^{nd}$ floor, and a finished dryvit exterior wall.
Keywords
Jaecheon sports center fire; Fire investigation; Fire case analysis; Catastrophic fire;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 E. P. Lee, "Analysis of the Causes of Catastrophic Damage of Goyang Bus Terminal Fire and the Preventive Measures for Similar Catastrophic Fires", Journal of Scientific Criminal Investigation, Vol. 12, No. 1, p. 46 (2018).
2 E. P. Lee, "Analysis of the Working Conditions of Fire Protection Systems in the Goyang Bus Terminal Building Fire", Fire Science and Engineering, Vol. 32, No. 3, pp. 98-99 (2018).
3 S. H. Lee, "Theory and Practice on Fire Investigation", Donghwa Technology Publishing Company, pp. 25-26 (2012).
4 S. B. Choi and D. M. Choi, "A Study on Fire Risk of Apartment House with Pilotis Structure - Focused on the Fire case of Uijeongbu-si Urban Livig Homes -", Fire Science and Engineering, Vol. 30, No. 3, pp. 48-54 (2016).   DOI
5 E. P. Lee, "Investigation and Analysis of Jecheon Sports Center Fire", Proceedings of 2018 Spring Annual Conference, Korean Institute of Fire Investigation, pp. 11-12 (2018).
6 E. P. Lee, "Problems and Measures to Prevent Recurrence of Cold Storage Fire", Journal of the Architectural Institute of Korea Planning & Design, Vol. 24, No. 12, pp. 39-46 (2008).
7 Y. B. Lee, C. H. Jeong, T. J. Jeong and H. Kim, "An Experimental Study on the Fire Characteristic of National Museum", Journal of the Fire Investigation Society & Equipment Technology, Vol. 3, No. 2, pp. 81-88 (2012).
8 S. B. Choi, "A Study on Fire Characteristics of Pilotis With Urban Lifestyle Housing Buildings", Doctor's Thesis, Gachon University, p. 18 (2018).
9 E. P. Lee, "Investigation and Analysis of a Goyang Bus Terminal Fire", Proceedings of 2017 Autumn Annual Conference, Korean Institute of Fire Investigation, pp. 13-42 (2017).
10 Icheon Fire Station, "White Paper on Iceon City Korea 2000 Cold Storage Fire" (2008).