Study on the Assessment of the Criteria on a Door Closer for the Optimum Design of the Access Door of a Smoke Control Zone  

Lee, Jae-Ou (Department of Fire Safety Engineering, Jeonju University)
Choi, Chung-Seog (Department of Fire Safety Engineering, Jeonju University)
Publication Information
Fire Science and Engineering / v.27, no.3, 2013 , pp. 66-71 More about this Journal
Abstract
The purpose of this study is to assess the criteria on a floor hinge and door closer for the optimum design of the access door of a smoke control room. The door opening force due to differential pressure is 60.75 N, 40.5 N, 32.91 N and 12.66 N when the differential pressure is 60 Pa, 40 Pa, 32.5 Pa and 12.5 Pa, respectively. The door opening force of the floor hinge and door closer to which the criteria of KS F 2806 are applied is 27.5 N, 40 N, 75 N, 100 N and 125 N for the Nos. 1, 2, 3, 4 and 5 class floor hinges and door closers, respectively. This study compared the differential pressure and opening force limits of floor hinges and door closers with the values specified in NFSC 501A and found that they exceeded the criteria specified in NFSC 501A. Therefore, it is necessary to reflect the differential pressure and smoke control wind speeds as well as the opening forces specified in NFSC 501A on the design of floor hinges and door closers. The installation conditions of floor hinges and door closers of access doors differ depending on the type and name of a smoke control damper. This study found that Nos. 1, 2 and 3 floor hinges and door closers could be installed for access doors with low differential pressure and that Nos. 1 and 2 floor hinges and door closers could be installed for access doors with normal differential pressure.
Keywords
Door closer; Optimum design; Smoke control zone; Floor hinge; Opening force; Differential pressure;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 Dougal Drysdale, "An Introduction to Fire Dynamics", Second Edition, Chapter 11, The Production and Movement of Smoke, pp. 386-401 (2002).
2 NEMA, "National Fire Safety Code, NFSC 501A of Stair Cases of Specific Fire Escape Stairs and Smoke Control Systems of Ancillary Rooms", Administrator at National Emergency Management Agency (2012).
3 NFPA 92A , Standard for Smoke-Control Systems Utilizing Barriers and Pressure Differences (2005).
4 BS EN 12101-6, Smoke and heat control systems. Specification for pressure differential systems (2005).
5 Korean Industrial Standard, "KS F 2806 Test Methods or Checking Floor-hinges and Door-closers Method", Korean Standards Association (2005).
6 Korean Industrial Standard, "KS F 4505 Door Closer", Korean Standards Association (2005).
7 H. J. Shin, J. H Choi and W. H. Hong, "Guidelines on Performance based Egress Design Criteria Considering the Risk Factors of a High-rise Building", Journal of Architectural Institute of Korea, Vol. 25, No. 7, pp. 139-148 (2009).   과학기술학회마을
8 J. O. Lee and C. S. Choi, "Study on the Analysis of Differential Pressure of the Access Door for a Smoke Control Zone and the Effectiveness of the Measurement Criteria of its Opening Force", Journal of Korean Institute of Fire Science & Engineering, Vol. 4, pp. 24-30 (2012).   과학기술학회마을   DOI   ScienceOn
9 S. H. Ro, S. W. Yoon and D. H. Rie, "Study for Using VR Techniques Performance Evaluation of the Elevator Evacuation", Journal of Korean Institute of Fire Science & Engineering, Vol. 1, pp. 13-18 (2011).   과학기술학회마을
10 S. M. Park, B. K. An and M. K. Kim, "Study for Pressurized Smoke Control System", Proceedings of 2009 Spring Annual Korean Institute of Fire Science & Engineering, pp. 118-124 (2009).
11 SFPE, "SFPE Handbook of Fire Protection Engineerng", Third Edition, Section 4, Chapter 12 "Smoke Control", Chapter 13, "Smoke Management in Covered Malls and Atria, pp. 274-310 (2002).