Abstract
Combustion characteristics of outdoor advertisement materials were evaluated for fire risk assessment about fire expanding. At this study, the flame retardancy and the limiting oxygen index (LOI) was measured by UL 94 and ASTM D 2863 respectively. At the result of flame retardancy, foamex was V-0 grade and those of others were out of grade. LOI measurement showed that the LOI of foamex was highest in the samples. The cone calorimeter test was done by ISO 5660-1 to find the combustion characteristics. The cone calorimeter test showed that the outdoor advertisement materials were not good to prevent of fire expanding. The time to ignition (TTI) of flex was the fastest and the peak heat release rate (PHRR) as well as the total heat release (THR) of acrylic panel was higher than those of others.
Keywords
Outdoor advertisement; Flame retardancy; Limiting oxygen index; Cone calorimeter;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 K. H. Oh, Y. Y. Choi and S. E. Lee, "A Study on the Combustion Characteristics of Wall Paper", Journal of Korean Institute of Fire Science & Engineering, Vol. 21, No. 1, pp. 90-97 (2007).
2 B. W. Lee, J. W. Lee, S. H. Sakong, H. S. Kim, B. H. Lee and H. J. Kim, "Burning Tests for Interior Flooring Materials", Journal of Korean Institute of Fire Science & Engineering, Vol. 22, No. 2, pp. 30-37 (2008).
3 H. P. Lee and Y. T. Kim, "A Study on the Fire Risk of Car Interior Materials", Journal of Korean Institute of Fire Science & Engineering, Vol. 24, No. 2, pp. 82-88 (2010).
4 ISO 5660-1, "Reaction to Fire Tests - Heat Release, Smoke Production and Mass Loss Rate - Part 1 : Heat Release Rate (Cone Calorimeter Method)", ISO (2002).
5 H. P. Lee and Y. J. Park, "A Study on Fire Characteristics of Carpet and Curtain Treated or Untreated with Flame Retardant", Journal of Korean Institute of Fire Science & Engineering, Vol. 21, No. 1, pp. 74-81 (2007).
6 M. J. Song, "Analysis on the Current Cityscapes in Korea and Their Problems", Journal of the Korea Contents Association, Vol. 8, No. 5, pp. 134-144 (2008).   DOI
7 S. G. Lee, "High Temperature Properties of Polymer Materials in Building Fire", Journal of Korean Architects, Vol. 136, No. 6, pp. 4-19 (1980).
8 D. S. Kim, J. S. Lee, Y. H. Jin, J. S. Lee and S. Y. Kim, "A Study on the Combustion Characteristics of Construction Materials", Fire Insurers Laboratories of Korea (2010).
9 B. S. Moon, N. S. Kim, N. W. Lee and S. D. Seol, "Evaluation of Fire Hazard about Polymer Materials Under High Temperature", Proceedings of 2005 Autumn Annual Conference, Korean Institute of Industrial Safety, pp. 407-412 (2005).
10 K. W. Lee and K. E. Kim, "Fire Characteristics of Plastic Insulating Materials from Cone Calorimeter Test", Journal of Korean Institute of Fire Science & Engineering, Vol. 17, No. 1, pp. 76-83 (2003).
11 B. W. Lee, S. P. Kwon, J. W. Lee, B. H. Lee, H. S. Kim and H. J. Kim, "Evaluation of the Burning Properties of Various Carpet Samples by using the Cone Calorimeter and Gas Toxicity Test", Journal of Korean Institute of Fire Science & Engineering, Vol. 23, No. 6, pp. 1-9 (2009).
12 N. W. Cho, D. H. Lee and E. H. Oh, "A Toxicity Evaluation for the Toxic Gases of Building Finish Materials", Journal of Korean Oil Chemists Society, Vol. 29, No. 1, pp. 129-140 (2012).