Abstract
Recently, evacuation safety of building resident become the major concern, as the building has been higher and more complicated. Required evacuation time using stairway is longer in high-rise buildings, moreover it is impossible for the disabled to evacuate by using stairway. For this reason the study on the effectiveness of using elevator for evacuation is progressing. This study shows the flow coefficient of hoistway when elevator is moving. The results of this study can be used for the study of elevator piston effect as basic data. Experiments were performed in 5 different hoistways at 3-story and 2-story buildings. According to the result of flow coefficient experiments, average flow coefficient is 0.954. Considering the $4{\sigma}$ to guarantee 99.99 % reliance, it is 0.86. This result is 3.6 % bigger than 0.83 that Klote and Tamura suggested. It represents that the maximum critical pressure is decreased about 7 % on the same condition of elevator and elevator shaft. When the smoke control performance of high-rise building is evaluated, the result is significant economically by applying a more realistic and less value of elevator piston effect.
Keywords
Elevator evacuation; Piston effect; Smoke control; Flow coefficient;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 G.T. Tamura and J.H. Klote, "Experimental Fire Tower Studies of Elevator Pressurization Systems for Smoke Control", ASHRAE Trans., Vol.93, Part.2, pp.2235-2256(1987).
2 G.T. Tamura and J.H. Klote, "Smoke Control Systems for Elevator Fire Evacuation", Elevators and Fire, pp.83-94(1993).
3 J.H. Klote and G.T. Tamura, "Elevator Piston Effect and the Smoke Problem", Reprinted from Fire Safety J., Vol.11, No.2, pp.227-233(1986).   DOI   ScienceOn
4 J.H. Klote, "An Analysis of the Influence of Piston Effect on Elevator Smoke Control", NBSIR 88-3751, National Bureau of Standard(1988).
5 변현섭, "엘리베이터 승강로 내에서의 피스톤 효과에 의한 압력변동에 관한 연구", 공기조화 냉동공학회 '97 하계학술발표회 논문집, pp.134-139(1997).
6 김학중, 김범규, 박용환, 임채현, "엘리베이터 승강로 형식별 압력변동에 관한 실험 연구", 한국화재소방학회 논문지, Vol.24, No.3, pp.139-144(2010).