Abstract
In this research, full-scale fire test was performed on a real house for the evaluation of the performance of waterworks direct-coupled sprinkler system. The fire was set to occur as spontaneous combustion as the cooking oil overheats. The size of house is $56m^2$ and it consists of a living room, a kitchen, and a room. In order to verify the performance of waterworks direct-coupled sprinkler system, it was installed in the kitchen. The result of the test showed that the fire started from the kitchen enlarged up to its ceiling but it was soon exhausted as the sprinkler started to work. The pressure of the waterworks was 0.28 MPa when the sprinkler operated, by which it verified that fire could go out even by waterworks pressure of the general residence.
Keywords
Waterworks direct-coupled sprinkler system; Full-scale fire test; Waterworks pressure;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 소방방재청, "2010년 화재현황통계"(2010).
2 소방방재청, "소방시설 설치유지 및 안전관리에 관한 법률", 제8조제1항.
3 소방방재청, "간이스프링클러설비의 화재안전기준 (NFSC103A)"(2009).
4 한국화재보험협회 번역판, "자동식스프링클러설비 핸드북", pp.769-904(2004).
5 이의평, "우리나라의 화재로 인한 사상자발생 실태에 관한 연구", 대한건축학회논문집계획계, Vol.22, No.4, pp.103-109(2006).
6 유용호, 권오상, 김흥열, "실물화재실험을 통한 공동 주택의 화재안정성 연구", 한국화재소방학회 논문지, Vol.23, No.5, pp.57-65(2009).
7 홍성우, 이영재, "단독주택의 간이스프링클러설비 적용에 관한 연구", 한국화재소방학회 논문지, Vol.22, No.4, pp.33-41(2008).