A Study on Evaluating the Fire Safety of the Regulation of Escape and Fire-Prevention from Enacting to Now - Focusing on the Hotel Building -  

Lee, Se-Myong (서울시립대학교 대학원 재난과학과)
Yoon, Myong-O (서울시립대학교 재난과학과)
Publication Information
Fire Science and Engineering / v.25, no.3, 2011 , pp. 28-41 More about this Journal
Abstract
Regulation of Escape and fire-prevention of Building of South Korea were enacted as a part of building codes in 1962. Since it was enacted, the law has gone through many changes. In this study, evaluated the fire safety of the law about the case of a hotel that the fire risk are expected to be higher whenever it was changed. As a result, the current law has gotten better in tire safety since it was enacted. However, especially it could be confirmed that the evacuation safety is insufficient in the lower level of hotel building. In the case of accommodation, because the occupants become aware of fire lately, they have not enough time to escape. Therefore, this study suggests that it is needed to come up with an effective counterplan about the interior finish materials, fire door and fire compartments that the smoke layer descending time is longer.
Keywords
Regulation of escape and fire-prevention of building; The fire safety; Escape time; Smoke layer descending time;