Abstract
Explosion limit and flash point are the major combustion properties used to determine the fire and explosion hazards of the flammable substances. In this study, in order to predict upper explosion limits (UEL) for acids and ketones, the upper flash point of these were measured under the VLE (vaporliquid equilibrium) state by using Setaflash closed cup tester (ASTM D3278). The UELs calculated by Antoine equation by using the experimental upper flash point are usually lower than the several reported UELs. From the given results, using the proposed experimental and predicted method, it is possible to research the upper explosion limits of the other flammable substances.
Keywords
Acids; Ketones; Upper flash point; Upper explosion limits (UEL); Setaflash closed cup tester (ASTM D3278);
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 J. Gmehing, U. Onken, and W. Arlt, "Vapor-Liquid Equilibrium Data Collection", 1, Part1-Part7, DECHEMA(1980).
2 NFPA, "Fire Hazard Properties of Flammable Liquid, Gases, and Volatile Solids", NFPA 325M (1991).
3 G.M. Zabetakis, "Flammability Characteristics of Combustible Gases and Vapors", US Bureau of Mines, Bulletin(1965).
4 K. Hasegawa and K. Kashiki, "A Method for Measuring Upper Flash Point", J. of Japan Society for Safety Engineering, Vol.29, No.5, pp. 332-340 (1990).
5 B.P. Mullins, "Bubble-points, Flammability-limits and Flash-points of Petroleum Products", Combustion Researches and Reviews, Butterworths, London (1957).
6 A.J. Pintar, "Predicting Lower and Upper Flammability Limits", Proc. Ind. Conf. on Fire Safety, Vol.28, Product Safety Corp., Sissonville WV(1999).
7 D.M. Ha, "Prediction of Upper Explosion Limits (UEL) by Measurement of Upper Flash Point Using Setaflash Apparatus for n-Alcohols", J. of the Korean Society of Safety, Vol.25, No.2, pp.35-40 (2010).
8 R.C. Lance, A.J. Barnard, and J.E. Hooymanm, "Measurement of Flash Points: Apparatus, Methodology, Applications", J. of Hazardous Materials, Vol.3, pp.107-119(1979).   DOI   ScienceOn
9 G.W. Jones, "Inflammation Limits and Their Practical Application in Hazardous Industrial Operation", Chem. Rev., Vol.22, No.1, pp.1-26(1938).   DOI
10 D.M. Ha, Y.S. Mok, and J.W. Choi, "Flash Points of a Flammable Liquid Mixture of Binary System", HWAHAK KONGHAK, Vol.37, No.2, pp.146-150 (1999).
11 Y. Iwata, et al., "Lower and Upper Flash Points of Flammable Liquids with Flame-Suppressing Agents", J. of Fire Sciences, Vol.17, pp.459-476(1999).   DOI   ScienceOn
12 V. Monakhov, "Method for Studying the Flammability of Substances", Published for U.S. National Bureau of Standard by American Publishing Co. New Delhi, India(1985).
13 Y.S. Mok, J.W. Choi, Y.I. Kim, I.G. Choi, and D.M. Ha, "Study on the Flash Point Determination 2- Proanol-Toluene Mixture", J. of the Korean Institute for Industrial Safety, Vol.12, No.3, pp.114-119(1997).
14 R.E. Lenga and K.L. Votoupal, "The Sigma Aldrich Library of Regulatory and Safety Data, Volume I-III", Sigma Chemical Company and Aldrich Chemical Company Inc.(1993).
15 柳生昭三, "蒸氣の爆發限界", 安全工學協會(1979).
16 F.P. Lees, "Loss Prevention in the Process Industries Vol. 1", 2nd ed., Oxford Butterworth-Heinemann (1996).
17 A.M. Kanury, "SFPE Handbook of Fire Protection Engineering; Ignition of Liquid Fuels", 2nd Ed., SFPE(1995).
18 V. Babrauskas, "Ignition Handbook", FSP & SFPE (2003).