Browse > Article

Validation of FDS for the Pool Fires within Two Rooms  

Bae, Young-Bum (한국원자력안전기술원)
Ryu, Su-Hyun (한국원자력안전기술원)
Kim, Yun-Il (한국원자력안전기술원)
Lee, Sang-Kyu (한국원자력안전기술원)
Keum, O-Hyun (한국원자력안전기술원)
Park, Jong-Seok (한국원자력안전기술원)
Publication Information
Fire Science and Engineering / v.24, no.5, 2010 , pp. 60-67 More about this Journal
Abstract
Fire model shall be verified and validated to reliably predict the consequences of fires within its limitations. Generally the verification and validation procedures are conducted by comparison with experimental test data. This study aims to evaluate predictive capabilities of FDS in the pool fire with two rooms and the sensitivity between input parameters such as heat release rate and ventilation rate and the output values like temperature, concentration, and heat flux. The predictive capabilities of FDS will be evaluated by comparing FDS simulation results with PRISME experimental data which result from the international fire test project. The sensitivity analysis will be conducted to decide which one of input parameters affects outcomes by comparison of FDS results with ${\pm}$ 10% changes of input parameter. From this study, the FDS predictive capabilities are within 20% error range. Heat release rate as input parameter affects most of outcomes and flow rate only has relation with concentration of oxygen and combustion products.
Keywords
Fire Dynamics Simulator (FDS); Pool fire; Validation;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Laurent Audouin, "Functional Specification for the test matrix in PRISME DOOR Experiments SEMIC- 2006-146-PRISME-2006-07"(2006).
2 윤명오, 고재선, 박형주, 박성은, "지하공동구 화재실험 및 시뮬레이션에 의한 화재 실험 예측 평가", 한국화재소방학회지, Vol.15, No.1, pp.22-33(2001).
3 박원희, 김동현, 장희철, 김태국, "지하철 역사 승강장 화재발생시 열/연기 거동 분석을 위한 실험 및 수치 연구(I)", 한국화재소방학회지, Vol.20, No.3, pp.9-14(2006).   과학기술학회마을
4 김봉찬, 신이철, 정기창, 김홍, 권영진, "단일 화재구역의 실물화재 실험에 대한 FDS 해석", 한국화재소방학회 추계학술논문발표회, pp.80-85(2008).
5 Standard Guide for Evaluating the Predictive Capability of Deterministic Fire Models, ASTM E1355-05a, ASTM, West Conshohocken, PA(2005).
6 D.T. Guttuk and D.A. White, "Liquid Fuel Fires", Section 2-15, The SFPE Handbook of fire Protection Engineering, 3rd Edition.
7 Young Bum Bae, et al., "Simulation of Pool Fire with Two Rooms using FDS Model", Proceedings of the SAREK, 2008 summer annual conference, pp.1332-1337.
8 K. McGrattan and G. Forney, "Fire Dynamics Simulator (Version 5.3) User's Guide", NIST Special Publication 1019, National Institute of Standards and Technology, Gaithersburg, MD(August, 2005).
9 J.X. Wen, et al., "Validation of FDS for the Prediction of Medium-scale Pool Fires", Fire Safety Journal 42(2007).
10 A. Tewarson, "Generation of Heat and Chemical Compounds in Fires", Section 3-4, The SFPE Handbook of fire Protection Engineering, 3rd Edition.
11 W. Le Saux, "PRISME DOOR programme-PRS D3 test report, DPAM/SEREA-2006-34 2, PRISME-014"(2006).
12 H. Pretrel, "PRISME-SOURCE BIS-Test Report DPAM/SEREA-2007-107-PRISME22"(2007).
13 NUREG-1824, "Verification and Validation of Selected Fire Models for Nuclear Power Plant Applications", U.S. Nuclear Regulatory Commission, Washington, DC(Jan. 2006).
14 K. McGrattan, "Fire Dynamics Simulator (Version 5.3) Technical Reference Guide", NIST Special Publication 1018, National Institute of Standards and Technology, Gaithersburg, MD(August, 2005).
15 H. Pretrel, "PRISME-SOURCE Program - Analysis Report SEREA-2007-116-PRISEM 23"(2007).
16 W. Le Saux, "Description of the DIVA facility, DPAM/SEREA-2006-157, PRISME-008"(2006).
17 NFPA 805, "Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants", National Fire Protection Association, Quincy, MA(2001).