Browse > Article

Optimum Fire Extinguishing Modeling using Impact Factor Analysis on Water Mist System of Pool Fire  

Hwang, Won-Jun (삼성전자)
Kim, Hwang-Jin (호서대학교 대학원)
Lee, Sung-Eun (호서대학교 산업안전기술연구센터)
Kim, Sung-Won ((주)파라다이스산업)
Oh, Kyu-Hyung (호서대학교 소방방재학과)
Publication Information
Fire Science and Engineering / v.23, no.5, 2009 , pp. 84-89 More about this Journal
Abstract
In this study, the fire extinguishing experiment was performed using a water mist nozzle with variation of factors which affect on the extinguishing time. The variables were distance from nozzle center to fire location, droplet size, height of nozzle and opening or not. With the experimental data, interaction and sensitivity between factors were analysed with Mini tab and deduce a optimum model of fire extinguishing of water mist system. Based on the experiment and modeling of fire extinguishing with water mist system, the most important factor on extinguishing time is the distance from the center of nozzle to fire and the opening effect was small compare with other factors.
Keywords
Water mist; Factor analysis; Mini tab; Extinguishing model;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 J.R. Mawhinney and Gerard G. Back, 'Water Mist Fire Suppression System', The SFPE Handbook of Fire Protection Engineering 3rd edition, pp.4-311 (2002)
2 W.J. Hwang and K.H.Oh, 'Experimental study on the Fire Extinguishing Characteristics of water Mist System', J. of Korean Institute of Fire Science and Engineering, Vol.23, No.2, pp.82-84(2009)
3 황원준, '포소화약제를 이용한 고압미분무수 소화시스템의 소화성능향상', 호서대학교 박사학위논문 (2009)
4 K.D. Lee, 'Performance of Fire Extinguishing of Water Mist Nozzle for Power Transformer Fire Scenario', J. of the Korean Society of Safety, Vol.21, No.6, pp.46-54(2006)
5 D.J. Rasbash, Z.W. Rogowski and G.W.V. Stark, 'Mechanism of Extinction of Liquids Fuels with Water Sprays', Combustion and Flame, Vol.4, pp. 223-234(1960)   DOI   ScienceOn
6 L. Liu and A. Kim, 'A Review of Water Mist Fire Suppression Systems -Fundamental Studies', J. of Fire Protection Engineering, Vol.10, No.3, pp.32-50 (2000)   DOI
7 이레테크 미니텝 사업팀, '새 MINI TAB 실무완성', (주)이레테크(2005)
8 삼성전자 6시그마 아카데미, 'Black Belt DMAIC 간접과정', Rev.8.0, pp.341-362(2007)
9 한국소방검정공사, '수동식 소화기의 형식승인 및 검정기술기준 (KOFEIS 0901)', 한국소방검정공사 (2000)
10 M.B. Kim and Y.J. Jang, 'Water Mist Fire Suppression (1) - A Personal Computer', J. of Korean Institute of Fire Science and Engineering, Vol.13, No.3, pp.27-33(1999)