Browse > Article

The Study of Development and Calibration for the Real Scale Fire Test Facility  

Yoo, Yong-Ho (한국건설기술연구원 화재설비연구부)
Kim, Heung-Youl (한국건설기술연구원 화재설비연구부)
Shin, Hyun-Jun (한국건설기술연구원 화재설비연구부)
Publication Information
Fire Science and Engineering / v.22, no.1, 2008 , pp. 37-44 More about this Journal
Abstract
The reduced scale fire test provides basic data but it is not enough to analysis real fire problem directly because there is no exact analogy theory between a real fire and the reduced scale model. Therefore, we have developed the 10 MW large scale calorimeter in order to real scale fire test. This advanced large scale calorimeter used for physical properties such as a heat release rate, based upon consumption of $O_2$ method. Using the heptane pool fire, we carried out the calibration in order to evaluation for heat release rate. It is approve that this facility has the reliability and it is capable of applying to the advance fire research in the future.
Keywords
Real scale fire test; Large scale calorimeter; Heat release rate; Consumption of $O_2$;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 이의주, "화재연구를 위한 대형콘칼로리미터의 설계", 한국화재소방학회논문지, Vol.20, No.4, pp.65-71 (2006)   과학기술학회마을
2 NIST, "The NIST 3 Megawatt Quantitative Heat Release Rate Facility - Description and Procedures", NIST Report(2004)
3 ASHRAE, "1993 ASHRAE HANDBOOK - FUNDANENTALS(1-P Edition)"(1993)
4 G. Heskestad, "A Fire Products Collector for Calorimeter into the MW Range", FM Technical Report(1981)
5 한국화재보험협회, "SFPE 방화공학 핸드북"(2005)
6 유용호, 김흥열, 신현준, 류상훈, "실물화재실험을 위 한 라지콘칼로리미터의 개발", 한국화재소방학회 2007 춘계학술발표대회 논문집(2007)
7 Bjorn Karlsson, James G. Quintiere, "Enclosure Fire Dynamics"(2000)
8 신현준, "화재안전기술의 선진화를 향한 거보", 건설 기술정보, pp.1-5(2004)
9 B. J. McCaffrey and G. Heskestad, "Robust Bidirectional Low-Velocity Probe for Flame and Fire Application", Combust. Flame, Vol.26, No.1, pp.125-127(1976)   DOI   ScienceOn
10 V. Babrauskas and S. J. Grayson, "Heat Release in Fires", Elsevier(1992)
11 M. Dahlberg, "The SP Industry Calorimeter for rate of Heat Release Measurements up to 10 MW", SP Report(1992)