Browse > Article

The Assessment of Fire Suppression Capability of Water-Mist System for Machinery Engine Room  

Choi, Byung-Il (한국기계연구원 에너지기계연구센터)
Han, Yon-Shik (한국기계연구원 에너지기계연구센터)
Oh, Chang-Bo (한국기계연구원 에너지기계연구센터)
Kim, Myung-Bae (한국기계연구원 에너지기계연구센터)
Kim, Chang ((주)WIN)
Publication Information
Fire Science and Engineering / v.21, no.2, 2007 , pp. 111-117 More about this Journal
Abstract
Full scale fire suppression test by water mist system were performed in machinery engine room ($20m{\times}15m{\times}10m$) according to IMO MSC/circ. 1165. The K-factor and operating pressure were 2.4 and 80 bar respectively. To assess the prediction capability of numerical simulation, FDS simulation was performed at the same operating condition with the full scale experiment. It was found that FDS simulation had the limitation for the fire extinguishing time prediction but was able to predict the spatial temperature distribution.
Keywords
Water mist; Full scale fire test; Numerical simulation;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 최병일, 한용식, 김명배, '변압기실 화재에 대한 미분무수 소화시스템의 적용 - 냉각특성을 중심으로(Part2)', 한국화재소방학회논문지, Vol. 19, No. 4, pp.37-41(2005)   과학기술학회마을
2 K.B. McGrattan, 'Fire Dynamics Simulator (Version 4), Technical Reference Guide', NIST Special Publication 1018, National Institute of Standards and Technology, Gaithersburg, Maryland, July(2004)
3 Imo Msc/circ. 1165, Alternative Arrangements for Halon Fire-Extinguishing Systems in Machinery Spaces and Pump-rooms(2005)
4 지역산업기술개발사업 중간보고서, '선박용 첨단 소화시스템의 소화성능평가 및 설계해석기술개발', 산업자원부(2006)
5 SFPE Handbook of Fire Protection Engineering 3rd edition, NFPA(2002)
6 K.B. McGrattan, 'Fire Dynamics Simulator (Version 4), User's Guide', NIST Special Publication 1019, National Institute of Standards and Technology, Gaithersburg, Maryland, July(2004)
7 NFPA 750, Standard on Water Mist Fire Protection Systems, 2000 ed., NFPA
8 G.P. Forney and K.B. McGrattan, 'User's Guide for Smokeview Version 4', NIST Special Publication 1017, National Institute of Standards and Technology, Gaithersburg, Maryland, July(2004)
9 S.C. Kim and H.S. Ryou, 'The Effect of Water Mist on Burning Rates of Pool Fire', Journal of Fire Sciences, Vol. 22, pp.305-323(2004)   DOI   ScienceOn
10 G. Grant, J. Brenton, and D. Drysdale, 'Fire Suppression by Water Spray', Progress in Energy and Combustion Science, Vol. 26, pp.79-130(2000)   DOI   ScienceOn
11 G. Santos, 'Water Mist Technology for Under Ground Transportation Systems', International Water Mist Conference(2003)
12 한용식, 최병일, 김명배, '변압기실 화재에 대한 미분무수 소화시스템의 적용 - 소화특성을 중심으로(Part1)', 한국화재소방학회논문지, Vol. 19, No. 4, pp.32-36(2005)   과학기술학회마을
13 노재성, 양승신, 김동현, 정우성, 장용준, 유홍선, '중저압 물분무를 이용한 객차내 화재진압에 관한 실험 및 수치해석적 연구', 한국철도학회논문집, Vol. 9, No. 3, pp.291-297(2006)   과학기술학회마을