Browse > Article

Primary Fire Behavior of Compounded Multiplex Theater with Various Fire Conditions  

Park, Yong-Hwan (호서대학교 소방방재학과)
Publication Information
Fire Science and Engineering / v.21, no.1, 2007 , pp. 1-6 More about this Journal
Abstract
This paper investigated the fire and smoke behavior in the compounded multiplex theater using FDS with various spacial and boundary conditions to ensure the fire safety of the multiplex. The results showed that more rapid temperature increase and smoke can be induced near the exit door for the lower fire load duo to the horizontal smoke movement. The overuse of fire resistants can generate more smoke while delaying combustion rate, which can give adverse effect to the evacuation. The mal-function of the exhaust fan would obstruct smoke exhaust but also retard the function of sprinkler head.
Keywords
Multiplex; Modeling; Fire behavior; Smoke; Exhaust fan;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 김종훈, '스프링클러 반응 시간 예측에 대한 화재 모델의 비교', 한국화재소방학회논문지, Vol. 15, No. 2, pp.46-52(2001)
2 조성우, '개구부와 열원의 위치에 따른 연기 이동에 관한 연구', 한국화재소방학회논문지, Vol. 16, No. 4, pp.7-14(2002)
3 BFRL, User's Guide for Smokeview v4, NIST Special publication 1017(2004)
4 허준호, '복합상영관 화재에 대한 화재모델링의 적용', 한국화재소방학회논문지, Vol. 18, No. 1, pp.42-48(2004)
5 BFRL, FDS(v4) Users Guide, NUST Special publication 1019(2005)