Browse > Article

Effect of Positive Pressure Ventilator Tilting Angle on the Flame Suppression and Smoke Density  

Kim, Sung-Won (충북대학교 안전공학과)
Lee, Kyoung-Duck (충북대학교 안전공학과)
Shin, Chang-Sub ((주)거송시스템)
Publication Information
Fire Science and Engineering / v.20, no.4, 2006 , pp. 135-142 More about this Journal
Abstract
The experiment applied Positive Pressure Ventilation to rapidly exhaust heat and smoke inside the construction in the fire was done. Changes of heat discharge and smoke density were measured, with the various blowing condition like a fan tilting angle to find the effect of the parameter. Experimental apparatus were with PPV and water mist system for better efficiency, and investigate the effect of heat discharge and smoke removal. In the experiment, flame temperature has decreased when PPV was applied. Smoke density, generated from fire also decreased dramatically and the efficiency showed the highest rate at $0^{\circ}$ tilting angle. In addition, combination of PPV and water mist system highly improved the efficiency of evacuation on heat and smoke density, clearly was influenced by the tilting angle.
Keywords
Positive Pressure Ventilation; Water mist; Fire suppression; Tilting angle;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Rimen, J., 'The Use of Positive Pressure Ventilation in Firefighting Operations', Fire Engineers, 60(206), pp.7-13(2000)
2 Ingason, H. and Fallberg, R., 'Positive Pressure Ventilation in Single Medium-Sized Premises', Fire Technology, Vol. 38, pp.213-230(2002)   DOI   ScienceOn
3 鈴木弘昭, 敏 'ウャ-タ-ミスト(マイクロフォグ) による 消火に關する硏究開發(その1)', 消防檢定協會, Vol. 7, pp.20-23(1997)
4 Victor, J. A., 'Use of Positive Pressure Ventilation (PPV) fans to Reduced the Hazards of Entering Chemically Contaminated Building', U.S. Army Edgewood Chemical Biological Center(ECBC), Report No. ECBC-TR-065(2000)
5 Rimen, J., 'An Assessment of the Use of Positive Pressure Ventilation in Domestic Properties', FRDG Publication Number 17/96(1996)
6 신창섭, 이경덕, '방사특성 변화에 따른 미세물분의 소화특성', 한국화재.소방 학회, Vol. 15, No 4, 2001
7 Ertel, M. and Berk, G. C., 'Firefighting', The Goodheart-Willcox Company, Inc.(1998)
8 www.firetactics.com
9 Tuomisaari, M., 'Smoke Ventilation on Operational Fire Fighting', VTT Publication 326, Technical Research Center of Finland(1997)
10 NFPA, 'The SFPE Handbook of Fire Protection Engineering'(2002)
11 Mittendorf, J., 'Positive Pressure Training Manual of Tempest', Tempest Tech. Co.(1992)