Abstract
This paper evaluates the fire safety level of eight pump rooms in the nuclear power plant using a fire model, CFAST We estimate the Conditional Core Damage Probability (CCDP) of each room based on the analyzed results of CFAST Eight rooms located on the primary auxiliary building of the nuclear power plant are high pressure safety injection pump room A/B, low pressure safety injection pump room Am. containment sprdy pump room A/B, and motor-driven auxiliary feed water pump room A/B. The upper layer gas temperature of each room is estimated and the integrity of cable is reviewed. Based on the results, the integrity of the cable located at the upper part of compartment is maintained without thermal damage. The Conditional Core Damage Probability Is reduced to half of the old values. Accordingly, the fire safety assessment for eight pump rooms using the fire model will be capable of reducing the uncertainty and to develop a more realistic model.
Keywords
Citations & Related Records
연도 인용수 순위
  • Reference
1 원자력발전소용 케이블 설명서, LG Cable(2003)
2 Fire PRA Implementation Guide, TR-105928, EPRI (1995)
3 이윤환 외 3, '화재모델 CFAST를 이용한 원전 화재 구역의 CCDP 평가', 한국화재소방학회논문지, Vol. 18, No 4, pp.64-71(2004)
4 Supporting Guidance for Implementation of IMC 0609 Appendix F-Fire Protection Significance Determination Process (SDP), U. S. NRC(2004)
5 Han et al., 'KAERI Integrated Reliablity Analysis Code Package (KIRAP) Release 2.0 User's Manual', KAERI/TR-361/93, KAERI(1993)
6 NSAC-178L, Fire Event Database for U.S. Nuclear Power Plants, Electric Power Research Institute, January(1993)
7 WHC-SD-SQA-ANAL-501, Fire Protection Guide for Waste Drum Storage Array, September(1996)