Browse > Article

A Study of the Application of Inert Gas Generator to the Fire Extinguishing System  

Han Yong-Shik (한국기계연구원 환경에너지기계연구본부)
Kim Myoung-Bae (한국기계연구원 환경에너지기계연구본부)
Kim Su-Yong (한국기계연구원 환경에너지기계연구본부)
Publication Information
Fire Science and Engineering / v.19, no.2, 2005 , pp. 69-74 More about this Journal
Abstract
A study of the utilization of inert gas generator(IGG) that generates a large amount of inert gas for the fire extinguishing equipment was performed. In this study, the fire extinction performance of gas generated from a 1GG which is implemented to a gas turbine was investigated. A simulated mixture gas of which composition is the same as that of the gas generated from ICG was used in all experiments. First, the extinction concentration was measured using a cup burner method. The extinction design concentration and the volume of extinction space was calculated by applying the obtained extinction concentration to a method recommended by NFPA 2001. In practical respects, the fire extinction performance of IGG-generated gas was confirmed through the fire suppression experiment within a $2m\times2m\times2m$ room.
Keywords
Citations & Related Records
연도 인용수 순위
  • Reference
1 NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems(1996)
2 UL 1058, Haligenated Agent Extinguishing System Units(1995)
3 청정소화약제 INERGEN 소화설비, 한국화재소방학회(청정소화약제 및 시설기준)(1995)
4 FIS 002, 가스계 소화설비의 성능기준에 관한 인정기준, 한국소방검정공사(2000. 10. 9)
5 김재덕, '가스계 소화시스템의 평가', 화재소방학회지, Vol. 1, No.1, pp.10-18(2000)
6 ISO 6183, Fire Protection Equipment-Carbon Dioxide Extinguishing Systems for Use on Premises-Design and Installation, 1990(E)