A Study on the Analysis of Damage Cause for MOF Installed in 22.9 kV Power Receiving System  

Kim Hyang-Kon (전기안전연구원(한국전기안전공사 부설))
Shong Kil-Mok (전기안전연구원(한국전기안전공사 부설))
Kim Dong-Ook (전기안전연구원(한국전기안전공사 부설))
Choi Chung-Seog (전기안전연구원(한국전기안전공사 부설))
Publication Information
Fire Science and Engineering / v.19, no.1, 2005 , pp. 93-98 More about this Journal
Abstract
The purpose of this paper is to judge the damage cause of instrument transformer(MOF; Metering Out Fit) installed in 22.9kV power receiving system. In the three-dimensional analysis of the restored MOF, the damage pattern progressed from inside to outside, there was no damaged part in the upside. The resistance of the carbonized middle part is roughly $100\kappa\Omega$ and the exothermic temperature at inside is presumed as about $300\~800^{\circ}C$ in the result of metallurgical structure analysis. The structure and the composition rate on metal surface by SEM is similar. In the result of FT-IR analysis, we can observe the absorbtion peak at $1500cm^{-1}\;and\;1730 cm^{-1}$ is small. The high exothermic peak showed at the center part of the coil in the result of DTA.
Keywords
Citations & Related Records
연도 인용수 순위
  • Reference
1 최충석 외 5, '전기화재공학', 도서출판 동화기술, pp. 189-198(2004)
2 길형준 외 3, '건설현장의 수전설비 및 배.분전반의 현장실태 분석', 한국조명.전기설비학회 춘계학술대회 논문집, pp.335-340 (2004)
3 V. Babrauskas, 'Fires due to Electric Arcing: Can 'Cause' Beads be Distinguished from 'Victim' Beads by Physical or Chemical Testing', Fire and Materials, pp.189-201(2003)
4 송길목 외 3, '트래킹에 의해 열화된 페놀수지의 탄화 특성', 대한전기학회, Vol. 53C, No.1, pp.1-7 (2003)
5 L.D. Chua, 'Introduction to Nonlinear Network Theory', McGraw Hill(1969)
6 C.S. Choi et al., 'The Analysis of Dendrite Structure of Electric Wire Melted by Fusing Current', 2003 J-K Joint Sysp. on ED&HVE, pp.145-148 (2003)
7 P.D. Peterson, 'Computer Aided Design of Ferroresonant Voltage Regulators', IEEE. Magazine, Vol. MAG-11, pp.71-79(1975)
8 한국전기안전공사, '전기재해 통계분석', pp.10-50 (2003)
9 Kerstin Kunde et al., 'Damping Ferroresonance in Transmission Networks', Electron, Vol. 13, Iss. 11, pp.37-40(1997)
10 C.S. Choi et al., 'The Statistical Analysis and Investigation of Field Condition About Electrical Shock Accidents and Risk Factors in Temporary Power Installations', International Journal of Safety, Vol. 2, No.2, pp.22-28 (2003)
11 Sheera Knecht et al., 'Fusing Current of Short Aluminum Bond Wire', 1996 InterSociety Conference on Thermal Phenomena, pp.329-333(1996)
12 최충석 외 2, '누전차단기 외함 전원측 단자사이의 트래킹에 의한 탄화특성 분석', 한국화재소방학회논문지 , Vol. 17, No.4, pp.13-19(2003)