Browse > Article

A Fire Risk Assessment of Substrate for Fire Resistant Painted  

Park Young-Keun (방재시험연구원)
Lee Doo-Hyung (방재시험연구원)
Yoon Myung-O (서울시립대학교 방재공학과)
Hyun Seong-Ho (경민대학 소방과학과)
Publication Information
Fire Science and Engineering / v.19, no.1, 2005 , pp. 51-58 More about this Journal
Abstract
In this paper, The experimental materials of painted fire resistant paint on substrate, FRP, PVC, AL and stainless steel that fire resistant paint developed newly were evaluated as the hazard elements : the fire resistibility of the materials, fire spread test of flame, the oxygen index, flammability, the smoke density. the toxicity index from it when it burned. As a result of the experiments, the AL and the stainless steel were passed of fire resistant class 1, the FRP, the AL, and the stainless steel were ignited of fire spread test of flame, all the experimental materials showed about $50\%$ of oxygen index, V-0 of flammability, and 43-338 of maximum smoke density at flaming mode used smoke density chamber. Also, they showed that the toxicity index of combustion products were 0.57-1.12.
Keywords
Citations & Related Records
연도 인용수 순위
  • Reference
1 행정자치부 소방국, '2002화재통계년보' (2003)
2 KS F 2271 : 건축물의 내장재료 및 구조의 난연성 시험방법 (1998)
3 BS 6853 : Code of Practice for Fire Precautions in the Design and Construction of Passenger Carrying Trains (1999)
4 이덕희, 이철규, 정우성, 김선옥, '철도차량 내장재의 화재안전도 평가방법 연구', 한국 화재.소방학회춘계학술논문발표회 논문집, pp.338-344(2003)
5 UL 94 : Test for Flammability of Plastic Materials for Parts in Devices and Appliances (1984)
6 ISO 4589-2 : Plastics-Determination of Flammability by Oxygen Index (1984)
7 IMO Resolution A.653(16) : International Code for Application of Fire Test Procedures(1989)
8 Marcelo M. Hirschler, 'Fire Hazard and Toxic Poxic Potency 0.1 the Smoke from Burning Materials', Advances in Combustion Toxicology, Vol. 2, pp.229-230(1990)
9 ASTM E 662 : Standard Test Method for Specific Optical Density of Smoked by Solid Materials (2003)
10 ISO 5658-2 : Plastics - Determination of Burning Behaviour by Oxygen Index - Part 2: Ambient - Temperature Test(1996)