Browse > Article

Combustion Characteristics of Fiber Reinforced Plastic by Cone Calorimeter  

이근원 (한국산업안전공단 산업안전보건연구원)
김관응 (한국산업안전공단 산업안전보건연구)
이두형 (한국화재보험협회 부설 방재시험연구워)
Publication Information
Fire Science and Engineering / v.18, no.2, 2004 , pp. 67-72 More about this Journal
Abstract
This study describes to assess combustion characteristics of fiber reinforced plastic (FRP) that is used an elements of building or structure in workplace. The combustion characteristics of the fiber reinforced plastic were carried out using by a Cone Calorimeter according to ISO 5660 standard. As the results of this study, the time to ignition and heat release rate of the fiber reinforced plastic was differ with heat flux of irradiance and content of flame retardant agent. The heat release rate of the fiber reinforced plastic was increased with increasing heat flux of irradiance. The flashover propensity of the fiber reinforced plastic using time to ignition and peak heat release rate was examined according to classification method by R.V. Petrella.
Keywords
Fiber reinforced plastic; Time to ignition; Cone Calorimeter; Heat release rate; flashover;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 G. Gallina, E. Bravin, C. Badalucco, G. Audisio, M. Armanini, and A. De Chirico, 'Application of Cone Calorimeter for the Assessment of Class of Flame Retardant for Polypropylene', Fire and Materials, Vol. 22, pp.15-18(1998)   DOI   ScienceOn
2 이근원, 김관응, '발포 플라스틱의 착화특성 및 연소가스 분석', 산업안전학회지, Vol. 16, No. 1, pp.48-52(2001)
3 Babrauskas and S. J. Grayson, Heat Release in Fires, Elselvier Science Publishing Co., New York (1992)
4 이근원, 김관응, '콘칼로리미터를 이용한 플라스틱 단열재의 화재특성', 한국화재.소방학회 논문지, Vol.17 No.1, pp 76-83(2003)
5 Petrella, R.Y., The Assessment of Full-scale Fire Hazards from Cone Calorimeter Data, Journal of Fire Sciences, Vol. 12, pp.14-43(1994)   DOI   ScienceOn
6 ISO 5660-1, Reaction to Fire, Part 1. Rate of Heat Release from Building Products (Cone Calorimeter), Genever(1993)
7 U. Sorathia, G. Long, T. Gracik, M. Blum, and J. Ness, 'Screening Tests for Fire Safety of Composites for Marine Applications', Fire and Materials, Vol. 25, pp.215-222(2001)   DOI   ScienceOn
8 이근원, '산업용 단열재의 화재위험 특성에 관한 연구'. 연구원 2000-18-138, 한국산업안전공단 산업안전보건 연구원(1999)