Browse > Article

Experiments on the Behavior of Underground Utility Cable in Fire  

박승민 (㈜안국 E&C)
김운형 (경민대학 소방과학과)
윤명오 (서울시립대학교)
Publication Information
Fire Science and Engineering / v.16, no.2, 2002 , pp. 75-80 More about this Journal
Abstract
In this paper, some experiments of a heat release rate and toxicity for underground utility 22.9kv cable in fire was conducted and analysed applying plume equation and smoke chamber test separately, A 22.9 ㎸ power cable is selected for testing heat release in ISO 9705 geometry and toxicity production is measured with NES 713 (British-Naval Engineering Standard)test. In test results, Cable heat release reached about 60 ㎾ above 1.2 m from heptane pan and CO generated lethal concentration under 30 min. exposure condition.
Keywords
Underground utility cable; Plume equation; NES 713 test; CO lethal concentration;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Gunnar Heskestad, 'Fire Plumes', SFPE Handbook of Fire Protection Engineering, Section 2 Chapter 2, 2nd Edition(1995)
2 김운형, 김현우, 현성호, 이창우, '건축재료의 연기 위험도 실험', 한국화재소방학회 춘계 학술발표회(2000.4)
3 홍경표, 이영재, 김선정, '지하공동구의 연소방지설비에 관한 연구', 2001년도 한국화재소방학회 추계학술논문발표회, pp.286-287(2001)
4 김운형, 김태수, 김상욱, '전력용 케이블의 열빙출량측정', 한국화재소방학회 추계학술발표대회, pp.280-283(2001)
5 V. Babrauskas, 'Heat Release in Fires', Elsevier Applied Science(1992)
6 박승민, 김운형, J. R. Mawhinney, '공동구의 미분무 소화설비 적용', 한국화재소방학회, 추계학술대회 논문집, pp.294-300(2001)
7 NES 713(Naval Engineering Stmdard 713), 'Determination of the toxicity index of the products of combustion from small specimens of materials Issue 3', March(1985)
8 김윤희, '지하공동구의 소방 및 안전대책에 관한 검토', 소방안전, 제58호(1999)
9 조영길, '전력케이블의 화염전파 특성에 관한 연구', 건국대학교 석사학위논문, (1998)
10 김운형, 김종훈, 박승민, 김태수, 민인홍, 전동일, 김상욱, '지하구 미분무수 소화설비 적용에 관한 연구', 한국화재소방학회, 제16권, 제1호(2002. 3)