Abstract
This paper includes new nozzle design, basic design factors of water mist system that minimize a thermal damage of cable causing business interruption and applying underground utility tunnel. A underground concrete structure (2.5 m(H)$\times$2.5 m(W)$\times$25 m(D)) is constructed in order to test a nozzle performance. Under the designing fire scenario, critical thermal damage of cable sheath ($400^{\circ}c$) reached within a 2 minutes with unsuppressed fire, but type 1 nozzle (SMD 470 $\mu{m}$) and type 2 nozzle (SMD 650 $\mu{m}$) control cable temperature below $400^{\circ}c$. A system performance and fundamental design factors; K factor, flow rate, spray angle, size distribution, nozzle pressure, spray density are analyzed and proposed for system optimization.
Keywords
Underground utility tunnel; Nozzle performance; Thermal damage of cable basic design factors of water mist system;
Citations & Related Records
연도 인용수 순위
  • Reference
1 김운형, J. A. Milke, 'Water Mist Fire Suppression for Raised Subfloor Spaces', International Symposium on Fire Science & Technology, pp.617-624, Korea(1997)
2 J. R. Mawhinney, B. Z. Dlugogorski, and A. K. Kim, 'A Closer Look at the Fire Extinguishing Properties of Water Mist', Fire Safety Science Proceedings of the Fourth International Symposium, pp.47-60(2000)
3 J. R. Mawhinney and J. K. Richardson, 'A Review of Water Mist FireSuppression Research & Development', Fire Technology, Vol 33, No1, pp.54-90(1997)   DOI   ScienceOn
4 NIST Report of Test FR 4000, 'Determination of Water Spray Drop Size & Velocity from a Low Pressure, High Momentum, Water Mist Nozzle, NIST(1995)
5 Zhigang Lui, Andrew K. Kim, 'A Review of Water Mist Fire Suppression Technology: Part II Applications Studies', Journal of Fire Protection Engineering, Vol. II, pp.16-42(2001)
6 J. R. Mawhinney, 'Principles of Water Mist Fire Suppression Systems', NFPA Handbook - 18th Edition(1997)
7 박승민, 김운형, J. R. Mawhinney, '공동구의 미분무 소화설비 적용', 한국화재소방학회, 추계학술대회 논문집, pp.294-300(2001)
8 김운형, 김태수, 김상욱, '전력용 케이블의 열방출량 측정', 한국화재소방학회 추계학술 발표대회 pp.280-283,(2001)
9 UL 199 - A Method of Measuring Water Density Distribution
10 NFPA 750, Standard on Water Mist Fire Protection Systems, pp.37-41, 2000, Edition