A study on the Prediction of Explosion Risk for the Low Pressure Natural Gas Facilities with Different Explosion Conditions  

Han, Sangil (Department of Chemical Engineering, Changwon National University)
Lee, Dongwook (School of Chemical & biomolecular Engineering, Pusan National University)
Hwang, Kyu-Suk (School of Chemical & biomolecular Engineering, Pusan National University)
Publication Information
Journal of the Korean Institute of Gas / v.20, no.3, 2016 , pp. 59-65 More about this Journal
Abstract
It is imperative to use suitable explosion proof equipments to prevent explosion in different gas facilities. There is no technical standard for the classification of hazardous areas though standard of explosion proof is regulated. In this study, we have adopted Industrial Standard KS to develop the methodology for the prediction of the explosion risk in the natural gas facility with low pressure using the important factors including hole size, hypothetical volume, validation of ventilation effectiveness. The applicability of the developed methodology was evaluated by the comparison with the data obtained from experiments of natural gas explosion.
Keywords
Natural gas; Explosion risk; hypothetical volume; hazardous areas;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 KGS GC201, "Code for explosion-proof electrical equipment of gas facilities", KGS GC201, (2013)
2 KS C IEC 60079-10-1, "Explosive atmospheres-Part- 10-1 : Classification of areas", Korea Industrial Standard, (2012)
3 Kang, S. M., Cheon, W. W., Choi, S. W., and Hwang, G. Y., "Electrical installations in hazardous area", Korea Occupational Safety and Health Agency, (2014)
4 KGS FS552, "Facility/Technical/Inspection Code for governors of general urban gas business", KGS Code, (2015)
5 Ivings, M. J., and Klsey A., "Technical input on ventilation effectiveness for area classification guidance EI15'' Health and Safety Executive Research Report, RR993, (2014)
6 Ivings, M. J., Clarke, S., and Gant, S. E., "Area Classification for secondary releases from low pressure natural gas systems", Health and Safety Executive Research Report, RR630, (2008)
7 Yim, J. P., and Chung, C. B., "A study on Classification of explosion hazardous using lighter than air gases", Journal of the Korean Society of Safety, 29(2), 24-30, (2014)   DOI
8 Kwon, J., "A Study on the establishing of the explosion-hazardous area of boiler room on the city gas-using facility", M.S. Thesis, Seoul National University of Technology, Seoul, Korea, (2014)
9 EI part 15, "Area classification code for installations handling flammable fluids", 3rd edition, The Energy Institute, (2005)