The power supply system is one of the most important infrafacilities which should maintain their inherent function during and after earthquakes. This study was performed to analyze dynamic characteristics and seismic performance of Korean typical 154kV transformer porcelain bushing. For the purpose of this study, actual 154kV porcelain bushings were selected and tested on the shaking table. The vibration tests consist of modal identification tests, seismic performance tests, and fragility tests. The sine sweep waves, artificial earthquake waves, and continuous resonant sine waves were used as shaking table motions. This paper describes the test specimens, shaking facilities, and test methods. Natural frequencies and damping ratios of the bushing have been evaluated from the experimental data. The failure mode and the performance level of the Korean transformer bushing have been first identified in this study.
Keywords
power supply system; transformer bushing; dynamic property; seismic performance; vibration test; modal identification; vibration frequency; damping ratio; failure mode;
Citations & Related Records
연도 인용수 순위
  • Reference
1 IEEE, IEEE Recommended Practice for Seismic Design of Substations, IEEE Std 693-1997, Institute of Electrical and Electronics Engineers, Inc., 1997
2 The STAR SystemTM, User Manual, Spectral Dynamics, Inc., 1996
3 전력연구원, '내진설계기준 설정에 따른 송변전설비의 안전도 평가', 최종보고서, 산업자원부, 20004
4 日本電氣協會,費電所等におけゐ電氣設備の冊震設計指針, JEAG 5003, 1999
5 전력 연구원, '송. 변전설비 내진설계기준 설정 연구', Technical Report, 01전력연-단601, 한국전력공사 전력연구원, 2001
6 전력연구원, 송변전설비 내진설계 실무지침서(안), 한국전력공사 전력연구원, 2003
7 Kiureghian, A. D., Sackman, J. L. and Hong, K. J., 'Interaction in Interconnected Electrical Substation Equipment Subjected to Earthquake Ground Motions,' PEER-1999/01, Pacific Earthquake Engineering Center, University of California, Berkeley, 1999
8 Gilani, A. S., Chavez, J. W., Fenves, G. L. and Whittaker, A. S., 'Seismic Evaluation of 196kV Porcelain Transformer Bushings,' PEER-1998/02, Pacific Earthquake Engineering Center, University of California, Berkeley, 1999
9 Bendat, J. S. and Piersol, A. G., Random Data - Analysis and Measurement Procedures, 3rd Ed., John Wiely & Sons, Inc., 2000
10 Gilani, A. S., Whittaker, A. S., Fenves, G. L. and Fujisaki E., 'Seismic Evaluation of 550kV Porcelain Transformer Bushings,' PEER-1999/05, Pacific Earthquake Engineering Research Center, University of California, Berkeley, 1999
11 한국전기연구소, 전기재료편람, 제3장 절연재료, 데이컴인터내셔널. 1990
12 Littl, J. N. and Shure, L., Signal Processing Toolbox User's Guide for Use with MATLAB, The Math Works, Inc., 1993