Seismic Response Estimation of Water Extinguishing Facilities using Shaking Table Tests  

Nam, Min-Jun (성균관대학교 u-City 공학과)
Park, Seung-Hee (성균관대학교 사회환경시스템공학과)
Kim, Dong-Joon (파라다이스산업 기술연구소)
Choi, Jun-Sung (한국유지관리(주))
Publication Information
Journal of the Earthquake Engineering Society of Korea / v.16, no.4, 2012 , pp. 9-18 More about this Journal
Abstract
In this study, a shaking table test was performed for the evaluation of water extinguishing facilities. Water extinguishing facilities, such as a general pipe, a seismic pipe (Loof type) and a pump, were used in the experiment. This captured the dynamic characteristics of water extinguishing systems by earthquake records at El-Centro with a 50%, 70%, 100%, 120% level. As a result, seismic type facilities have excellent seismic performance compared to general facilities. By using the acceleration response spectrum, not only is the performance evaluation of water extinguishing facilities able to be determined, but also the deformation of facilities in low earthquake levels can be known. This proposed approach can determine the seismic performance evaluation of water extinguishing facilities and verify seismic performance criteria.
Keywords
Water extinguishing facilities; Shaking table test; Acceleration response spectrum; Seismic design; Seismic performace evaluation;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 이현진, 신이철, 이재영, 서동구, 한병찬, 김재환, 권영진 "소방 설비 내진설계에 관한 각국 기준 비교 연구," 2008년 춘계학술발표회 눈문집, 한국화재소방학회, 238-241, 2008.
2 김종부, 스프링클러 설비의 내진 설계 방법론 연구, 석사학위논문, 서울시립대학교, 2011.
3 김두기, 구조동역학, 구미서관, 서울, 474-504, 2009.
4 소방방재청 재난안전기술연구개발 "한반도 활성단층과 연구 현황," 한국방재학회지, Vol. 11, No. 1, 117-123, 2011.
5 신이철, 한병찬, 박선규, 이현진, 권영진 "소방시설 내진설계의 필요성과 기준정비에 관한 연구," 한국 화재소방학회지 논문집, Vol. 23, No. 2, 6-12, 2009.
6 MATLAB, The Language of Technical Computing, Mathworks, 2011.
7 정진환, 김남식, 김인태, 최형석, 박찬영, "KOCED 지진실험 센터," 대한토목학회지, Vol. 57, No. 8, 43-49, 2009.
8 건설교통부, 내진설계기준연구(II), 1997.
9 대한건축학회, Korea Building Code, 국토해양부, 2009.
10 Roberto Villaverde "Simple method to estimate the seismic nonlinear response of nonstructural components in buildings," Engineering Structures, Vol. 28, No. 8, 1209-1221, 2006.   DOI   ScienceOn
11 Elliott GOODWIN, Emmanuel MARAGAKIS, Ahmad ITANI "Seismic evaluation of hospital piping systems," Earthquake Engineering, 13th World Conference on Earthquake Engineering, Paper No. 1081, 2004.
12 ICC, International building code (IBC), International Code Council, INC, 2012.
13 Farzad Naeim, The Seismic Design Handbook Second Edition, Kluwer Academic Publishers, 681-722, 2001.
14 윤종구, 김동수 "국내 지반특성에 적합한 설계지반운동 결정 방법에 대한 연구," 한국지진공학회 논문집, Vol. 8, No. 3, 23-32, 2004.
15 김장훈 "비구조요소의 내진설계," 대한건축학회 논문집, Vol. 48, No. 8, 53-56, 2004.
16 남민준, 박승희, 윤종구, 서춘교, "진동대 실험을 통한 수계형 소화설비의 내진성능 평가," 2012년 학술발표회 논문집, 한국지진공학회, 121-124, 2012.