Seismic Fragility Analysis of Substation Systems by Using the Fault Tree Method  

Kim, Min-Kyu (한국원자력연구원 종합안전평가부)
Choun, Young-Sun (한국원자력연구원 종합안전평가부)
Choi, In-Kil (한국원자력연구원 종합안전평가부)
Oh, Keum-Ho (국립방재연구소)
Publication Information
Journal of the Earthquake Engineering Society of Korea / v.13, no.2, 2009 , pp. 47-58 More about this Journal
Abstract
In this study, a seismic fragility analysis was performed for substation systems in Korea. To evaluate the seismic fragility function of the substation systems, a fragility analysis of the individual equipment and facilities of the substation systems was first performed, and then all systems were considered in the fragility analysis of the substation systems using a fault-tree method. For this research, the status of the substation systems in Korea was investigated for the classification of the substation systems. Following the classification of the substation systems, target equipment was selected based on previous damage records in earthquake hazards. The substation systems were classified as 765kV, 345kV, and 154kV systems. Transformer and bushing were chosen as target equipment. The failure modes and criteria for transformer and bushing were decided, and fragility analysis performed. Finally, the fragility functions of substation system were evaluated using the fault tree method according to damage status.
Keywords
substation system; Seismic fragility function; fault tree method; failure probability; damage status;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 Murota, N., Feng, M. Q. and Liu, G. Y., Experimental and Analytical Studies of Base Isolation Systems for Seismic Protection of Power Transformers, Technical Report MCEER-05-0008, MCEER, 2005
2 FEMA(미국재난관리청), HAZUS99 User's Manual, 1999
3 Hwang, H.H.M and Chou, T., Evaluation of Seismic Performance of and Electric Substation using Event/Fault Tree Technique, Probabilistic Engineering Mechanics, Vol. 13, No. 2, 1998, pp. 117-124   DOI   ScienceOn
4 박영준,조호현,박원석,고현무,변압기의 병렬운전을 고려한 국내 345kV 초고압 전력망의 지진 재해 신뢰성 평가, 한국지진공학회 논문집, 제10권, 제3호, 2006, pp. 13-20   과학기술학회마을   DOI
5 한전전력연구원, 송변전설비의 내진설계기준 설정 연구, 2001
6 Ang, A. H-S., Tang, W. H., Probability concepts in engineering planning and design, J. Wiley and Sons, New York, , 1975
7 Ang, A.H.-S., Pires, J.A. and Villaverde, R., A Model for the Seismic Reliability Assessment of Electric Power Transmission Systems, Reliability Engineering and System Safety, Vol. 51, 1996, pp. 7-22   DOI   ScienceOn
8 (社)日本原子力學會標準, 原子力發展所의地震에起因한確率論的安全性評價實施基準, (2006)
9 Reed, J.W. and Kennedy, R.P., Methodology for Developing Seismic Fragilities, Palo Alto, California: Electric Power Research Institute (EPRI), prepared by Jack R. Benjamin and Associates, Inc., 1994, TR-103959
10 고현무,김영호,박영석,“지진 재해에 대한 전력 송전 네트워크 시스템의 신뢰성 평가 모형”, 한국지진공학회, Vol. 7, No. 2, 2003, pp. 93-102   과학기술학회마을   DOI
11 조양희, 조성국, 진동시험에 의한 154kV 변압기 부싱의 동특성 분석 및 내진성능 평가,한국지진공학회 논문집,제10권 제5호, 2006, pp. 107-115   과학기술학회마을   DOI
12 Hwang, H.H.M and Huo, J-R., Seismic Fragility Analysis of Electric Substation Equipment and Structures, Probabilistic Engineering Mechanics, Vol. 13, No. 2, 1998, pp. 107-116   DOI   ScienceOn
13 Camensig, C., Bresesti, L., Clementel, S. and Salvetti, M., Seismic Risk Evaluation for High Voltage Air Insulated Substations, Reliability Engineering and System Safety, Vol 55, 1997, pp. 179-191   DOI   ScienceOn