Abstract
This paper proposes a fault diagnosis method of the line-to-line voltage sensors in 3-phase AC/DC pulse width modulation (PWM) converters. The line-to-line voltage sensors are an essential device to obtain the information of the grid voltages for controlling the 3-phase AC/DC PWM converters. If the line-to-line voltage sensors are mismeasured by various faults, the voltage sensors can obtain wrong information of the grid voltage. It has an adverse effect on the control of the converter. Therefore, the converter causes the unbalance input AC current and the DC-link voltage ripple in the 3-phase AC/DC PWM converter. Hence, fast fault detection and fault tolerant control are needed. In this paper, the fault diagnosis method is proposed and verified through simulations and experiments.
Keywords
3-phase PWM converter; Fault diagnosis; voltage sensor;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 R. L. de Araujo Ribeiro, C.B. Jacobina, E.R.C. da Silva, and A.M.N. Lima, "Fault detection of open-switch damage inverters using wavelet and SVM," journal of Power Electronics, Vol. 9, No.3, pp. 377-385, Jun. 2009
2 Young-Jong Ko and Kyo-Beum Lee, "Fault Diagnosis of a Voltage-Fed PWM Inverter for a Three-Parallel Power Conversion System in a Wind Turbine," Journal of Power Electronics, vol. 10, no. 6, pp. 686-693, Nov 2010   DOI   ScienceOn
3 M. Beltrao de Rossiter Correa, C. Brandao Jacobian, E.R. Cabral da Silva and A.M Nogueira Lima, " An Induction Motor Drive System with Improved Fault Tolerance" IEEE Trans. Ind. Appl., vol. 37, no. 3, pp.873-879, May/Jun.2001   DOI   ScienceOn
4 Yuwen Hu, Lanhong Zhang, Wenix Huang and Feifei Bu, "A Fault-Tolerant Induction Generator System Based on Instantaneous Torque control(ITC)"," IEEE Trans. Energy Conversion, vol. 25, no. 2, pp.412-421,Jun.2010   DOI   ScienceOn
5 B.A Welchko, T.A. Lipo, T.M. Jahns and S.E.schulz, "Fault Tolerant Three-Phase AC Motor Drive Topologies: A Comparision of Feature, Cost, and Limitation", IEEE Trans. Power Elec., vol. 19,no. 4,pp.1108-1116, July.2004.   DOI   ScienceOn
6 C.B.Jacobian, I.S Freitas, T.M. Oliveria, E.R.C. da Silva, and A.M.N. Lima, "Fault-Tolerant Voltage-Fed PWM Inverter AC Motor Drive Systems", IEEE Trans. Ind. Elec., vol. 51, no. 2, pp. 439-446, Apr.2004.   DOI   ScienceOn
7 Won-Sang Im, Jang-Sik Kim, Jang-Mok Kim, Dong-Choon Lee, and Kyo-Beum Lee, "Diagnosis methods for IGBT Open Switch Fault Applied to 3-phase AC/DC PWM Converter", Journal of Power Electronics, Vol. 12, No. 1,pp.120-127,Jan.,2012.   DOI   ScienceOn
8 Yongsug Suh and Thomas A. Lipo, "Control Scheme in Hybrid Synchronous Stationary Frame for PWM AC/DC Converter Under Generalized Unbalanced Operating Conditions" IEEE Trans. Ind. Appl., vol.42,no3,pp.825-835,May/Jun.2006   DOI   ScienceOn