Browse > Article

Behavior of Underground Flexible Pipes Subject to Vehicle Load (ll)-Based on Field Tests-  

이대수 (한전 전력연구원)
상현규 (한전 전력연구원)
김경열 (한전 전력연구원)
홍성연 (한전 전력연구원)
Publication Information
Journal of the Korean Geotechnical Society / v.19, no.5, 2003 , pp. 49-58 More about this Journal
Abstract
Underground flexible pipes for electric cables are subject to external loads and surrounding soil pressure. Particularly, strain of flexible pipes is of great concern in terms of safety and maintenance for electric cables. In this paper, stress and strain of flexible pipes with various installation depth are compared using traditional formula, FEM analysis, model soil box test and field test. from the findings of various analyses, considering the strain criteria-maximum 3.5%, it is suggested that flexible pipes can be buried at the depth of 80cm without additional soil improvement.
Keywords
Field test; Numerical analysis; Soil box test; Stress-strain diagram; Underground flexible pipe;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 /
[ 이이환(외 13인) ] / 지중관자재 적정규격 제정을 위한 기술 용역
2 파형강관의 시험시공 및 현장계측 연구 /
[ 김진만 ] / 한국토목학회 2000 학술발표회 논문집
3 지반침하가 매설배관의 건전성에 미치는 영향 /
[ 오규환 ] / 한국가스공사 건전성 진단워크숍
4 /
[ 조성수 ] / 지중배전 설계편람
5 /
[ 片岡折之 ] / 配電地中化における 車道下埋設 ケ-ブル 防護管の 淺層埋設の 檢討
6 PE파형관의 구조적 안정 검토 /
[ 김동수 ] / 전기통신연구 논문
7 차량하중을 받는 지중연성관의 거동특성 /
[ 이대수;상현규;김경열 ] / 한국지반공학회 논문집   과학기술학회마을
8 /
[ 건교부 ] / 도로교 표준시방서
9 매설흄관의 설계하중 결정에 관한 연구 /
[ 정성교 ] / 대한토질공학회 논문집   과학기술학회마을
10 뒷채움 다짐에 의한 횡방향 토압 /
[ 정성교 ] / 대한토목학회 논문집
11 /
[ 이시용 ] / 관로 포설공법의 개선연구