Browse > Article

Behavior of Underground Flexible Pipes Subject to Vehicle Load  

이대수 (한전 전력연구원)
상현규 (한전 전력연구원)
김경열 (한전 전력연구원)
Publication Information
Journal of the Korean Geotechnical Society / v.18, no.4, 2002 , pp. 65-73 More about this Journal
Abstract
Underground flexible pipes for electric cables are subject to external loads and surrounding soil pressure. Particularly, strain of flexible pipes is of great concern in terms of safety and maintenance for electric cables. In this paper, stress and strain of flexible pipes with various depth are compared using traditional formula, FEM analysis and model soil box test. The results show that theoretical values are more conservative in strain in comparison with model soil box test and FEM analysis. Considering the strain criteria - maximum 3.5%, flexible pipes can be buried at the depth of 40cm without additional soil improvement. From the result of this study, deformation formula compatible with the field condition was proposed.