A Comparative Analysis of Step and Touch Voltages Depending on Two Test Voltage Waveforms  

Jung, Kwang-Seok (Division of Electrical and Electronics Engineering, Korea Maritime University)
Cha, Sang-Wook (Division of Electrical and Electronics Engineering, Korea Maritime University)
Park, Dae-Won (Division of Electrical and Electronics Engineering, Korea Maritime University)
Kil, Gyung-Suk (Division of Electrical and Electronics Engineering, Korea Maritime University)
Oh, Jae-Geun (Division of Physics and Chemistry of Central District, National Forensic Service)
Publication Information
Transactions on Electrical and Electronic Materials / v.12, no.4, 2011 , pp. 152-155 More about this Journal
Abstract
This paper presents a comparative analysis on step and the touch voltages generated by either a sine and a ring wave voltage generator; this analysis was done as a basic study in order to develop a small and lightweight ground meter. A ring wave generator using pulsed power technology was fabricated; an experimental grounding system specified in Institute of Electrical and Electronics Engineers standards 80 and 81 was installed. The step and the touch voltages, which were measured using comparable a sine and a ring waves in terms of magnitude and frequency, were equal. Using pulsed power technology, the weight of the fabricated ring wave generator could be reduced to one-fifth of that of a sine wave generator. Consequently, if a ground meter adopts the ring wave instead of a sine wave, it will be possible to reduce the weight of a ground meter and improve the efficiency of measurement.
Keywords
Touch voltage; Step voltage; Ground meter; Ring wave generator; Pulsed power technology;
Citations & Related Records

Times Cited By SCOPUS : 0
연도 인용수 순위
  • Reference
1 IEEE Std. 81-1983. IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System. p. 18-26 [DOI: 10.1109/IEEESTD.1983.82378].   DOI
2 A. P. Meliopoulos and M. G. Moharam, IEEE Trans. Power App. Syst. PAS-102, 389 (1983) [DOI: 10.1109/TPAS.1983.317686].   DOI   ScienceOn
3 A. P. S. Meliopoulos, Power System Grounding and Transients: An Introduction (Marcel Dekker, New York, 1988) p. 5-20.
4 R. Morrison and W. H. Lewis, Grounding and Shielding in Facilities (Wiley, New York, 1990) p. 44-45.
5 R. Kosztaluk, R. Mukhedkar, and Y. Gervais, IEEE Trans. Power App. Syst. PAS-103, 3286 (1984) [DOI: 10.1109/TPAS.1984.318571].   DOI   ScienceOn
6 A. P. S. Meliopoulos, G. Cokkinides, H. Abdallah, S. Duong, and S. Patel, IEEE Trans. Power Del. 8, 1095 (1993) [DOI: 10.1109/61.252636].   DOI   ScienceOn
7 M. Khalifa, High-Voltage Engineering: Theory and Practice (Marcel Dekker, New York, 1990) p. 331-356.
8 A. D. Papalexopoulos and A. P. Meliopoulos, IEEE Trans. Power Del. 2, 1073 (1987) [DOI: 10.1109/TPWRD.1987.4308223].   DOI   ScienceOn
9 A. Geri, IEEE Trans. Power Del. 14, 1008 (1999) [DOI: 10.1109/61.772347].   DOI   ScienceOn
10 IEEE Std. 367-1996. IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage From a Power Fault. p. 2 [DOI: 10.1109/IEEESTD.1997.83838].   DOI
11 R. P. O'Riley, Electrical Grounding: Bringing Grounding Back to Earth, 6th ed. (Delmar Thomson Learning, Albany, NY, 2002) p. 40-43.
12 IEEE Std. 80-2000. IEEE Guide for Safety in AC Substation Grounding. p. 114 [DOI: 10.1109/IEEESTD.2000.91902].   DOI