Abstract
Many studies have been done on the application of residual charge measurement in cable degradation diagnosis. In this paper, the behavior of residual charges measured with water-tree degraded XLPE sheets and cable are discussed. At charge injection process, the charge is injected by applying dc voltage as a conventional method, suddenly cut-off ac voltage or impulse voltage. Therefore the residual charge is influenced by the applying process. At charge release process, transient dc current flows when applying ac high voltage and also ac high voltage superimposed to dc low voltage. From the results, new diagnosis method is suggested.
Keywords
Water-tree; Residual charge; Deterioration diagnosis; XLPE insulated cable;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Y. Ikeda and T. Tanaka, 'Diagnosis Method for Water Tree Aging of XLPE Cable and Development of Charge Measuring Device', CRIEPI Report W86008, in Japanese, 1986
2 Technical Report lEE Japan, II-266, in Japaness, 1988
3 Y. Ebinuma, Y. Kubota, J. Kawai, and Y. Fujiwar, 'Discussion on measurement method of insulation diagnosis for 22 kV XLPE cable', T.IEE Japan, Vol. 114-B, No.3, p. 305, 1994
4 J. Kawai, M. zablan, Y. Li, Y. Ebinuma, and Y. Fujiwara, 'Behavior of Space Charges During Residual Charge Measurement of Water Tree Degraded XLPE Cables', IEE of Japan Power & Energy '95, p. 233, 1995