Browse > Article
http://dx.doi.org/10.6113/JPE.2013.13.4.712

Control Method for Reducing the THD of Grid Current of Three-Phase Grid-Connected Inverters Under Distorted Grid Voltages  

Tran, Thanh-Vu (Dept. of Electrical Engineering, University of Ulsan)
Chun, Tae-Won (Dept. of Electrical Engineering, University of Ulsan)
Lee, Hong-Hee (Dept. of Electrical Engineering, University of Ulsan)
Kim, Heung-Geun (Dept. Of Electrical Engineering, Kyungpook National University)
Nho, Eui-Cheol (Dept. of Electrical Engineering, Pukyong National University)
Publication Information
Journal of Power Electronics / v.13, no.4, 2013 , pp. 712-718 More about this Journal
Abstract
This paper proposes a control method for reducing the total harmonic distortion (THD) of the grid current of three-phase grid-connected inverter systems when the grid voltage is distorted. The THD of the grid current caused by grid voltage harmonics is derived by considering the phase delay and magnitude attenuation due to the hardware low-pass filter (LPF). The Cauchy-Schwarz inequality theory is used in order to search more easily for the minimum point of the THD. Both the gain and angle of the compensation voltage at the minimum point of the THD of the grid current are derived with the variation of cut-off frequencies of the hardware LPF. Simulation and experimental results show the validity of the proposed control methods.
Keywords
Current control; Grid-connected inverter; Harmonic distortion; Total harmonic distortion (THD);
Citations & Related Records
연도 인용수 순위
  • Reference
1 F. Blaabjerg, Z. Chen, and B.S. Kjaer, "Power Electronics as efficient interface in dispersed power generation systems," IEEE Trans. Power Electron., Vol. 19, No. 5, pp. 1184-1194, Sep. 2004.   DOI   ScienceOn
2 B. Kroposki, R. Lasseter, T. Ise, S. Morozumi, S. Papathanassiou, and N. Hatziargyriou, "Making Microgrids Work." IEEE Power & Energy Mag., Vol.6, No.3, pp. 41-53, May/Jun. 2008.
3 IEEE standard for interconnecting distributed resources with electric power systems, IEEE Standard 1547.2, 2008.
4 J. Dannehl, F. W. Fuchs, and P. B. Thogersen, "PI state space current control of grid-connected PWM converter with LCL filters,." IEEE Trans. Power Electron., Vol. 25, No. 9, pp. 2320-2330, Sep. 2010.   DOI   ScienceOn
5 E. Twining and D. Grahamehs, "Grid current regulation of a three-phase voltage source inverter with a LCL input filter," IEEE Trans. Power Electron., Vol. 18, No. 39, pp. 888-895, May 2003.
6 J. Dannehl, C. Wessels, and F. W. Fuchs, "Limitations of voltage-oriented PI current control of grid-connected PWM rectifiers with LCL filters," IEEE Trans. Elect. Electron., Vol. 56, No. 2, pp. 380-388, Feb. 2009.   DOI   ScienceOn
7 D. N. Zmood and D. G. Holems, "Stationary frame current regulation of PWM inverters with zero steady-state error," IEEE Trans. Power Electron., Vol. 18, No. 3, pp. 814-822, May 2003.   DOI   ScienceOn
8 G. Shen, X. Zhu, J. Zhang, and D. Xu, "A new feedback method for PR current control of LCL filter-based grid-connected inverter," IEEE Trans. Elect. Electron., Vol. 57, No. 6, pp. 2033-2041, Jun. 2010.   DOI   ScienceOn
9 Q. N. Trinh and H. H. Lee, "Improvement of Current Performance for Grid Connected Converter Under Distroted Grid Condition," in Proceeding of RPG, pp.1-6, 2011.
10 X. Yuan, W. Merk, H. Stemmler, and J. Allmeling, "Stationary-frame generalized integrators for current control of active power filters with zero steady-state error for current harmonics of concern under unbalanced and distorted operation conditions," IEEE Trans. Ind. Appl., Vol. 38, No.2, pp. 523-532, Mar./Apr. 2002.   DOI   ScienceOn
11 Y. Sato, T. Ishizuka, K. Nezu, and T. Kataoka , "A new control strategy for voltage-type PWM rectifiers to realize zero steady-state control error in input current," IEEE Trans. Ind. Appl., Vol. 34, No.3, pp. 480-486, May/Jun. 1998.   DOI   ScienceOn
12 T. Abeyasekera, C. M. Johnson, D. J. Atkinson, and M. Armstrong, "Suppression of line voltage related distortion in current controlled grid connected inverters," IEEE Trans. Power Electron., Vol. 20, No. 6, pp. 1393-1401, Nov. 2005.   DOI   ScienceOn
13 P. Mattavelli, "A closed-loop selective harmonic compensation for active filters," IEEE Trans. Ind. Appl., Vol. 37, No.1, pp. 81-89, Jan./Feb. 2001.   DOI   ScienceOn
14 J. Miret, M. Castilla, J. Matas, J. M. Guerrero, and J. C. Vasquez, "Selective harmonic-compensation control for single-phase active power filter with high harmonic rejection," IEEE Trans. Ind. Electron., Vol.56, No.8, pp.31173127, Aug. 2009.   DOI   ScienceOn
15 M. P. Kazmierkowski, M. Jasinski, and G. Wrona, "DSP-based control of grid-connected power converters operating under grid distortions," IEEE Trans. Ind. Informat., Vol. 7, No. 2, pp.204-211, May 2011   DOI   ScienceOn
16 L.G. B. Rolim, D. R. da Costa, and M. Aredes, "Analysis and software implementation of a robust synchronization PLL circuit based on the pq theory," IEEE Trans. Ind. Electron., Vol.53, No.6, pp.1919-1926, Dec. 2006.   DOI   ScienceOn