Browse > Article

New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations  

Kim, Chan-Ki (KEPRI)
Kwon, Young-Hun (KEPCO)
Jang, Gil-Soo (Dept. of Elect. Eng., Korea University)
Publication Information
Journal of Power Electronics / v.7, no.3, 2007 , pp. 233-237 More about this Journal
Abstract
This paper deals with the new HVDC interaction which was observed in the Jeju-Haenam HVDC system. The interaction is not from a system malfunction or controller loop problem but from the change of AC network scheme and the network operating condition. We have found that the interaction is caused by the voltage oscillation between synchronous compensator and HVDC shunt reactor. We analyzed the cause of the interaction and suggested a solution.
Keywords
HVDC; Reasonance;
Citations & Related Records

Times Cited By Web Of Science : 0  (Related Records In Web of Science)
연도 인용수 순위
  • Reference
1 J. Reeve, J.A Baron and G.A Hnaley, 'A Technical Assessment of Artificial Commutation of HVDC Converters' IEEE Trans. PAS, Vol. PAS-87, no. 10, October 1968, pp 1830-1840   DOI
2 T. Jonsson, P-E. Bjorklund, 'Capacitor Commutated Converters for HVDC,' Stockholm power Tech. Conference, Stockholm, June 1995, pp.44-51
3 P. Kunder, Power System Stability and Control, ERPI, 1996
4 A.M. Gole and R.W. Menzies, 'Analysis of Certain Aspects of Forced Commutated HVDC Inverters,' IEEE Trans. PAS, Vol. PAS-100, NO.5, May 1981, pp 2258-2262   DOI