Abstract
The purpose of this study is to analyse the characteristics and spreading laws of parameters such as fire smoke, concentration of CO, visibility, and temperature at fire scene in high-rise residential buildings under the different conditions of fire doors and automatic fire extinguishing systems. Using Pyrosim to simulate diverse fire scenes in a high-rise apartment with corridors, to analyze the changes in those parameters. The results show that when a fire occurs, closing the fire-fighting corridor will increase the smoke temperature and concentration of CO in the stairwell, and reduce the height and visibility of the smoke layer; the automatic fire extinguishing system effectively suppresses the increase in the temperature of the fire smoke and the sedimentation of the smoke layer. Reasonable setting and operation of the automatic fire extinguishing system could effectively inhibit the spread of fire. Although closing fire corridor can slow down the direct upward spread of smoke through the corridor, it will force the fire smoke into the stairwell, which will seriously affect evacuation through the stairs. Therefore, in order to reduce risks, it is forbidden to close the fire doors of the firefighting corridor and stacking combustible materials in the corridor, Also, intensifying inspections and ensuring the normal operation of the automatic fire extinguishing system are indispensable. Based on the research results, the significance of installing fire-fighting facilities in the construction of high-rise apartments was discussed and proved.
Keywords
High-rise Apartments; Fire doors; Pyrosim; fire; simulation;
Citations & Related Records
연도 인용수 순위
  • Reference
1 HUGX.Researchonthefireofhighriseresidentialbuildingbasedonpyrosimnumericalsimulation[I]IOPConfer-enceSeries:EarthandEnvironmentalScience,2020,455(1):12059. https://doi.org/10.1088/1755-1315/45 5/1/012059   DOI
2 Huang Dong mei, Wang Xin qun, Min. A Study on the Influence of New Ventilation Area in Restricted Space [J]. Journal of China College of Metrology, 2014,25(3)308-313.
3 Ministry of Housing, Urban and Rural Construction, People's Republic of China. Code for fire protection design: GB50016-2014[S]. Beijing: China Planning Press, 2014.
4 Wang Yu, Zhou Yingtong, Qu Zhibeng, A Numerical Study on the Longitudinal Spread of Fire in High-rise Buildings with Corridor [J]. Journal of Shenyang University of Architecture, 2020, 36(6):1020-1026.
5 Fire simulation of high-rise houses based on Pyrosim. Building safety, 2020, 35(11): 22-25.
6 AHNC,KIMD,PARKC,etal.Experimentalandnu-mericalstudyofsmokebehaviorinhigh-risestairwellswithopenandclosedwindows[J].InternationalJournalofTher-malSciences,2020,157:106500.
7 KIMBG, YIMCH, PARKYH. Theinfluenceofwindconditionsontheperformanceofsmokeventilationinhigh-risebuildingfires[J]. FireScienceandEngineering, 2016, 30(1):63-73. http://doi.org/10.7731/KIFSE.2016. 30.1.036   DOI
8 Dai Changqing, Yuan Hui. FDS-based fire simulation of high-rise residential buildings[J]. Journal of Anhui University of Architecture, 2017,25(4):14-1.
9 Ministry of Housing, Urban and Rural Construction of the People's Republic of China. Code for design of automatic sprinkler fire extinguishing system: GB50084-2017[S]. Beijing: Output of China plan Publishers, 2017.
10 Xu Liang, Zhang He ping, Yang Yun, et al. Discussion on fire scene setting in performance fire protection design [J]. Firefighting Science and Technology, 2004, 23(2):129-132.
11 Yang fu qiang. Fire Prevention Course Design[ M]. Beijing: Chemical Industry Press, 2018:134-135.