Abstract
The purpose of this study is to analyze the safety of evacuation using the Pathfinder program for the alert at once, the priority alarm method, the priority alarm method for the four floors above, and the sequential priority alarm method, which is a modification of the priority alarm method specified in the tourist hotel building. Currently, in Korea's National Fire Safety Codes (NFSC), fire alarm methods are compulsorily applied differently depending on the number of floors and total floor area of a building. Although the growth rate is getting faster due to the diversification of building structures, it is still an obstacle to improving evacuation safety to comply with the standardized fire alarm method in NFSC. As a result of the experiment, the evacuation time was found to be faster with the priority alarm method for the four floors above than the priority alarm method applied to the specific firefighting object. Compared to the priority alarm method applied to the tourist hotel, which is a specific firefighting target with 5 or more floors and a total floor area of more than 3,000m2, the time was shortened by 3.7 seconds when measured by applying the priority alarm method for the four floors directly above. This indicates that it is necessary to take measures to select a fire alarm method suitable for the structure and environmental conditions of the building rather than applying the uniform NFSC regulations.
Keywords
Fire Alarm Method; Tourist Hotels; Evacuation Safety Evaluation; Sequential Priority Alarm;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Ministry of Government Legislation, "Enforcement Decree of the Act on Fire Prevention, Installation and Maintenance of Firefighting Facilities, and Safety Management," [15-2] Amended on 8. 27, 2021.
2 H. S, Han and C. H. Hwang, "Study on the Available Safe Egress Time(ASET) Considering the Input Parameters and Model Uncertainties in Fire Simulation," Fire Science and Engineering, Vol. 33, No. 3, pp. 112-120 (2019). https://doi.org/10.7731/KIFSE.2019.33.3.112.   DOI
3 National Information Center, "Building Act Enforcement Decree," 2021.
4 Ministry of Government Legislation, "Enforcement Decree of the Act on Fire Prevention, Installation and Maintenance of Firefighting Facilities, and Safety Management," [Annex 2] Amended on 8.7, 2021.
5 J. H. Heo and K. Jeong, "A study on the direction of evacuation evaluation according to the fire alarm method in performance-oriented design," Fire Science and Engineering, Vol. 35, No. 3, pp. 127-133. 2021. https://doi.org/10.7731/kifse.e7023a9e   DOI
6 D. K. Dong, Y. C. Ahn, S. G. Yeo, E. J. Kim and Y. S. Lee, "A Study on the Effective Evacuation Plan of High-rise Buildings by the Fire Alert System," Journal of the Korean Society for Power System Engineering, Vol. 22, No. 3, pp. 79-88, 2018. http://dx.doi.org/10.9726/kspse.2018.22.3.079   DOI
7 S. H. Moon, "A study on the evacuation safety according to priority alert method," Graduate School of Dongshin University. 2015.
8 S. Y. Kim and H. S. Kong, "Evacuation Safety Evaluation in the Event of a Fire in a Shopping Center with a Connected Passageway in Korea," Turkish Journal of Computer and Mathematics Education, Vol.12 No.5 (2021), 333-339. https://doi.org/10.17762/turcomat.v12i5.956   DOI
9 Gwangju Times. http://www.gjtnews.com
10 S. W. Gu and Y. J. Song, "A Study on the Fire Alarm System of Vertical Fire Spread Structure by Using FDS," Fire Science and Engineering, Vol. 30, No. 5, pp. 100-107, 2016. https://doi.org/10.7731/KIFSE.2 016.30.5.100   DOI
11 Fire Service Notification, "Building Act Article 2 Paragraph 1 No. 19," 2021.
12 Fire Service Notification, "Article 15 Paragraph 2 of the Rules on Standards for Evacuation of Buildings," 2021
13 Fire Service Notification, "Article 19," 2019.
14 H. Y. Jang and C. H. Hwang, "Revision of the Input Parameters for the Prediction Models of Smoke Detectors Based on the FDS," Fire Science and Engineering, 2017, vol. 31(2):44-51. https://doi.org/10.77 31/KIFSE.2017.31.2.044   DOI
15 J. J. Jeong, "Analysis of Evacuation Route Selection Pattern of Occupant according to Installation Type of Exit Light and Opening/Closing Direction of Door," Fire Sci. Eng., Vol. 33, No. 6, pp. 28-34, 2019. https://doi.org/10.7731/KIFSE.2019.33.6.028   DOI
16 H. J. Seo, H. Y. Lee, K. Y. Jeon, and W. H. Hong, "Installation status and improvement of evacuation safety facilities for the disabled in the underground space research on," Fall Proceedings of the Korean Fire and Fire Society, pp. 68, 2007.