Browse > Article
http://dx.doi.org/10.5370/JEET.2018.13.4.1450

Design of Direct-Current Fuzzy Controller for Mitigating Commutation Failure in HVDC System  

Gao, Benfeng (Department of Electronic Engineering, North China Electric Power University)
Yuan, Kewei (Department of Electrical Engineering, North China Electric Power University)
Dong, Peiyi (State Grid Baoding Electric Power Supply Company)
Luo, Chao (Electric Power Research Institute of China Southern Power Grid)
Zhao, Shuqiang (Department of Electronic Engineering, North China Electric Power University)
Publication Information
Journal of Electrical Engineering and Technology / v.13, no.4, 2018 , pp. 1450-1458 More about this Journal
Abstract
Commutation failures can deteriorate the availability of high-voltage direct current (HVDC) links and may lead to outage of the HVDC system. Most commutation failures are caused by voltage reduction due to ac system faults on inverter side. The commutation failure process can be divided into two stages. The first stage, from the occurrence to the clearing of faults, is called 'Deterioration Stage'. The second stage, from the faults clearing to restoring the power system stability, is called 'Recovery Stage'. Based on the analysis of the commutation failure process, this paper proposes a direct-current fuzzy controller including prevention and recovery controller. The prevention controller reduces the direct current to prevent Commutation failures in the 'Deterioration Stage' according to the variation of ac voltage. The recovery controller magnifies the direct current to speed up the recovery of power system in the 'Recovery Stage', based on the recovery of direct voltage. The validity of this proposed fuzzy controller is further proved by simulation with CIGRE HVDC benchmark model in PSCAD/EMTDC. The results show the commutation failures can be mitigated by the proposed direct-current fuzzy controller.
Keywords
HVDC; Commutation failure; Fuzzy controller; PSCAD/EMTDC; CIGRE;
Citations & Related Records
연도 인용수 순위
  • Reference
1 L. Zhang and L. Dofnas, "A novel method to mitigate commutation failures in HVDC systems," in Proc. IEEE Power Syst. Technology Conf, vol. 1, pp. 51-56, Oct. 2002.
2 F. Nozari, and H. S. Patel. "Power electronics in electric utilities: HVDC power transmission systems," Proceedings of the IEEE, vol. 76, no. 4, pp. 495-506, 1988.   DOI
3 J. Choi, G. Hwang, H. T. Kang, and J. H. Park, "Design of Fuzzy Logic Controller for HVDC Using an Adaptive Evolutionary Algorithm," IEEE International Symposium on Industrial Electronics Proceedings, vol. 3, pp. 1816-1821, 2001.
4 M. Szechtman, T. Wess, and C. V. Thio, "First benchmark model for HVDC control studies," Electra, vol. 135, no. 4, pp. 54-73, 1991.
5 L. Zhang and L. Dofnas, "A novel method to mitigate commutation failure in HVDC systems," IEEE Power System Technology Conf., vol. 1, pp. 51-56. Oct. 2002.
6 Z. X. Shao and X. Y. Li, "The HVDC Emergency Power Slaughter Support Adaptive Fuzzy Controller," Automation of Electric Power Systems. Nanjing, vol. 26, pp. 1-3, 2002.
7 H. X. Chen and T. Q. Liu, "An Auxiliary Fuzzy Control for Converter Substation In HVDC System," Power System Technology. Beijing, vol. 27, pp. 5-8, 2003.
8 X. F. Xu, X. Y. Li, Q. Yan, H. C. Liu, and L. Wang, "HVDC Fuzzy Controller to Improve Transient Stability," Relays, vol. 32, pp. 16-19, 2004.
9 C. V. Thio, J. B. Davies, and K. L. Kent, "Commutation failures in HVDC transmission systems," IEEE Trans. Power Del., vol. 11, no. 2, pp. 946-957, Apr. 1996.   DOI
10 P. Lv, M. Wang, and H. Xu, "Analysis of commutation failure reason in three Gorges-Guangdong HVDC system Echeng station," Relay (China), vol. 33, no. 18, pp. 75-78, Sep. 2005.
11 O. U. Kaijian, Ren Zhen, Jing Yong, "Research on commutation failure in HVDC transmission system part 1: commutation failure factors analysis," Electric Power Automation Equipment., vol. 23, no. 5, pp. 5- 8, 2003.
12 E. Rahimi, S. Filizadeh, and A.M. Gole, "Commutation failure analysis in HVDC systems using advanced multiple-run methods," Power Systems Transients (PST), pp. 19-23, 2005.
13 E. Rahimi, A.M. Gole, J. B. Davies, I. T. Fernando, and K. L. Kent, "Commutation failure in single- and multi-infeed HVDC systems," IEEE Trans. Power Del., vol. 26(1), pp. 378-384, 2011.   DOI
14 S. Tamai, H. Naitoh, F. Ishiguro, M. Sato, K. Yamaji, and N. Honjo, "Fast and predictive HVDC extinction angle control," IEEE Trans. Power Syst., vol. 12, no. 3, pp. 1268-1275, Aug. 1997.   DOI
15 Z. Wei, Y. Yuan, X. Lei, H. Wang, G. Sun, and Y. Sun, "Direct-current predictive control strategy for inhibiting commutation failure in HVDC converter," IEEE Trans. Power Syst., vol. 29, no. 5, pp. 2409- 2417, 2014   DOI
16 Sun, Y. Z, et al. "Design a Fuzzy Controller to Minimize the Effect of HVDC Commutation Failure on Power System," IEEE Transactions on Power Systems, vol. 23, no. 1, pp. 100-107, 2008.   DOI
17 Bauman, Jennifer, and M. Kazerani. "Commutation Failure Reduction in HVDC Systems Using Adaptive Fuzzy Logic Controller," IEEE Transactions on Power Systems, vol. 22, no. 4, pp. 1995-2002, 2007.
18 Wei, Zhinong, et al. "Direct-Current Predictive Control Strategy for Inhibiting Commutation Failure in HVDC Converter," IEEE Transactions on Power Systems, vol. 29, no. 5, pp. 2409-2417, 2014.   DOI
19 T. Machida and Y. Yoshida, "A method to detect the deionization margin angle and to prevent the commutation failure of an inverter for dc transmission," IEEE Trans. Power App. Syst., vol. PAS-86, no. 3, pp. 259-262, Mar. 1967   DOI
20 J. Bauman and M. Kazerani, "Commutation failure reduction in HVDC systems using adaptive fuzzy logic controller," IEEE Trans. Power Syst., vol. 22, no. 4, pp. 1995-2002, Nov. 2007.
21 T. Ahn, "Design of the Optimal Self-tuning Fuzzy-Pi Controller for Rectifier Current Control in HVDC System," Chinese Control Conference IEEE, pp. 1224-1227, 2006.
22 M. O. Faruque, Y. Zhang, and V. Dinavahi. "Detailed modeling of CIGRE HVDC benchmark system using PSCAD/EMTDC and PSB/SIMULINK," IEEE Transactions on Power Delivery, vol. 21, no. 1, pp. 378-387, 2006.
23 J. D. Ainsworth, "Proposed benchmark model for study of HVDC controls by simulator or digital computer," in Proc. CIGRE SC-14 Colloq. HVDC With Weak AC Systems, Maidstone, U.K., Sep. 1985.