Analysis of an Active Superconducting Current Controller (ASCC) Considering the Transient Stability and OCR Operation in Transmission and Distribution Systems  

Gusheh, Ahmad Ghafari (Young Researchers and Elite Club, Ramhormoz Branch, Islamic Azad University)
Soreshjani, Mohsen Hosseinzadeh (Department of Electrical Engineering, Ramhormoz Branch, Islamic Azad University)
Rahat, Omid (Young Researchers and Elite Club, Ramhormoz Branch, Islamic Azad University)
Publication Information
Journal of Electrical Engineering and Technology / v.11, no.3, 2016 , pp. 543-550 More about this Journal
Abstract
The Active Superconducting Current Controller (ASCC) is a new type of Superconducting Fault Current Limiters (SFCL) which can limit the fault current in different modes. It also has the particular abilities of compensating active and reactive powers for electrical networks. In this paper, it is confirmed that the performance of ASCC in different operating modes introduces a limiting impedance in series with the network which can even degrade the transient stability and the operation of the Over-Current Relays (OCR) employed in a power system. In addition, the model of a three-phase ASCC is simulated, and the effect of descriptive modes on the current limiting level is investigated. For the transient stability analysis, a single machine-infinite bus system is tested, and the effect of operation modes is studied based on an equal area criterion obtaining the critical time and the critical angle. Modifying the setting parameters of OCR such as time dial and pick-up current, the protective coordination is also studied in different operating modes.
Keywords
Active superconducting current controller; Fault current limiters; Over-current relay; Transient stability; Distribution system;
Citations & Related Records
연도 인용수 순위
  • Reference
1 J. Wang, L. Zhou, J. Shi, and Y. Tang, “Experimental investigation of an active superconducting current controller,” IEEE Trans. Appl. Supercond, vol. 21, no. 3, pp. 1258-1262, June 2011.   DOI
2 F. Moriconi, F. De La Rosa. F. Darmann, A. Nelson, and L. Masur, “Development and Deployment of Saturated-Core Fault Current Limiters in Distribution and Transmission Substations,” IEEE Trans. Appl. Supercond, vol. 21, no. 3, pp. 1288-1293, June 2011.   DOI
3 Y. Mo, D. Jiang, Z. Wu, “Study of the three-phase saturated transformer coupling new bridge-type SSFCL,” Int. Trans. Elec. Energy. Syst, vol. 24, no. 4, pp. 477-491, April 2014.   DOI
4 M. Song, Y. Tang, Y. Zhou, L. Ren, L. Chen, and S. Cheng, “Electromagnetic characteristics analysis of air core transformer used in voltage compensation type active SFCL,” IEEE Trans. Appl. Supercond, vol. 20, pp. 1194-1198, June 2010.   DOI
5 L. Chen, Y. J. Tang, M. Song, J. Shi, and L. Ren, “Parameter design and performance simulation of a 10 kV voltage compensation type active superconducting fault current limiter,” Physica C: Supercond., vol. 494, no. 15, pp. 349-354, November 2013.   DOI
6 L. Chen, J. Tang, J. Shi, Z. Sun, “Simulations and experimental analyses of the active superconducting fault current limiter,” Physica C, vol. 459, No. 1-2, pp. 27-32, August 2007.   DOI
7 L. Chen, Y. Tang, J. Shi, Z. Li, L. Ren, and S. Cheng, “Control strategy for three-phase four-wire PWM converter of integrated voltage compensation type active SFCL,” Physica C. vol. 470, no. 3, pp. 231-235, February 2010.   DOI
8 L. Chen, J. Tang, J. Shi, L. Rena, M. Song, S. Cheng, Y. Hu, X. Chen, “Effects of a voltage compensation type active superconducting fault current limiter on distance relay protection,” Physica C, vol. 470, no. 20, pp. 1662-1665, November 2010.   DOI
9 L. Chen, Y. Tang, J. Shi, N. Chen, M. Song, S. Cheng, Y. Hu, S. Chen, “Influence of a voltage compensation type active superconducting fault current limiter on the transient stability of power system,” Physica C., vol. 469, No. 15-20, pp. 1760-1764, October 2009.   DOI
10 B. Sung, D. Park, J. Park, T. Ko, “Study on a series resistive SFCL to improve power system transient stability: modeling, simulation and experimental verification,” IEEE Trans. Ind. Electron., vol. 56, no. 7, pp. 2412-2419, July 2009.   DOI
11 A. Ghafari, M. Razaz, G. Seifossadat and M. Hosseinzadeh, “Protective coordination of main and backup overcurrent relays with different operating modes of active superconducting current controller,” Maejo Int. J. Sci. Technol, vol. 8, no. 3, pp. 319-333, 2014.
12 J. S. Kim, S. H. Lim, and J. C. Kim, “Study on application method of superconducting fault current limiter for protection coordination of protective devices in a power distribution system,” IEEE Trans. Appl. Supercond, vol. 22, no. 3, pp. 5601504, June 2012.   DOI
13 S. H. Lim, J. S. Kim, and J. C. Kim, "Analysis on protection coordination of hybrid SFCL with protective devices in a power distribution system," IEEE Trans. Appl. Supercond. vol. 21, no. 3, pp. 2170-2173, December 2011.   DOI
14 M. Song, Y. Tang, J. Li, Y. Zhou, L. Chen, and L. Ren, “Thermal analysis of HTS air-core transformer used in voltage compensation ype active SFCL,” Physica C, vol. 470, no. 20, pp. 1657-1661, November 2010.   DOI
15 J. S. Kim, J. F. Moon, S. H. Lim, J. C. Kim, “Study on Selection of SFCLs Impedance for Protective coordination with Overcurrent Relay in a Distribution System,” Transm. And Distr. Conf. and Exp.: Asia and Pacific., pp. 1-4, 2009.
16 J. S. Kim, S. H. Lim, and J. C. Kim, “Study on protective coordination for application of superconducting fault current limiter,” IEEE Trans. Appl. Supercond, vol. 21, no. 3, pp. 2174-2178, June 2011.   DOI