Browse > Article
http://dx.doi.org/10.5370/JEET.2015.10.2.487

Power System Oscillations Damping by Robust Decentralized DFIG Wind Turbines  

Surinkaew, Tossaporn (Dept. of Electrical Engineering, King Mongkut's Institute of Technology Ladkrabang)
Ngamroo, Issarachai (Dept. of Electrical Engineering, King Mongkut's Institute of Technology Ladkrabang)
Publication Information
Journal of Electrical Engineering and Technology / v.10, no.2, 2015 , pp. 487-495 More about this Journal
Abstract
This paper proposes a new robust decentralized power oscillation dampers (POD) design of doubly-fed induction generator (DFIG) wind turbine for damping of low frequency electromechanical oscillations in an interconnected power system. The POD structure is based on the practical $2^{nd}$-order lead/lag compensator with single input. Without exact mathematical model, the inverse output multiplicative perturbation is applied to represent system uncertainties such as system parameters variation, various loading conditions etc. The parameters optimization of decentralized PODs is carried out so that the stabilizing performance and robust stability margin against system uncertainties are guaranteed. The improved firefly algorithm is applied to tune the optimal POD parameters automatically. Simulation study in two-area four-machine interconnected system shows that the proposed robust POD is much superior to the conventional POD in terms of stabilizing effect and robustness.
Keywords
Doubly-fed induction generator; Power oscillation damper; Inter-area oscillation; Robust control; Firefly algorithm;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 T. Surinkaew, I. Ngamroo, and W. Nakawiro, “Robust Power Oscillation Damper Design for DFIG-based Wind Turbine”, in Proc. 10th International Conference on ECTI-CON, 2013.
2 L. Yang, G. Y. Yang, Z. Xu, Z. Y. Dong, K. P. Wong, X. Ma “Optimal controller design of a doubly-fed induction generator with wind turbine system for small signal stability enhancement”. IET Gener Transm Distrb, no. 5, vol.4, pp.579-97, 2010.   DOI   ScienceOn
3 P. Kundur “Power system stability and control”, McGrawhill, 1994.
4 F. Milano “Power system modelling and scripting”, Springer, 2010.
5 S. Skoqestad, Postlethwaite I. “Multiple feedback control: analysis and design”, Wiley, 2005.
6 B.Chaudhuri, B.C. Pal, A.C. Zolotas, I.M. Jaimoukha, and T.C. Green, “Mixed-sensitivity approach to Hcontrol of power system oscillations employing multiple FACTS devices,” IEEE Trans. on Power Syst., vol. 18, no. 3, pp. 1149-1156, Aug. 2003.   DOI   ScienceOn
7 X.S. Yang. “Engineering optimization: an introduction with metaheuristic applications”, Wiley, 2010.
8 F. Milano “Power system analysis toolbox version 2.1.6”, 2011.
9 C. Jauch, T. Cronin, P. Sorensen, B.Jensen “A fuzzy logic pitch angle controller for power system stabilization”, Wind Energy, vol. 10, pp. 19-30, 2007.   DOI   ScienceOn
10 D. G. José Luis, G. B. Oriol, D. B. Fernando, S. Andreas “Power oscillation damping supported by wind power: a review”, Renewable and Sustainable Energy Reviews, vol. 16, pp.4982-93, Sept. 2012.   DOI   ScienceOn
11 H.T. Jadhav, R. Roy “A comprehensive review on the grid integration of doubly fed induction generator”, Int J Elect Power Energy Syst, vol.49, pp.8-18. July 2013.   DOI   ScienceOn
12 J.L. Dominguez-Garcia, O. Gomis-Bellmunt, L. Trilla-Romero, Junyent-Ferre A. “Vector control of squirrel cage induction generator for wind power”, Proc Int Conf Electrical Machines, 2010.
13 O. Anaya-Lara, F. Hughes, N. Jenkins, G. Strbag “Power system stabilizer for a generic DFIG-based wind turbine controller”, Proc 8th IEE Int Conf AC DC Power Trans, pp. 145-149, 2006.
14 F. Wu, Z. Zhang, K. Godfrey, P. Ju “Small signal stability analysis and optimal control of a wind turbine with doubly fed induction generator”, IET Gener Transm Distrib, no. 5, vol. 1, pp. 751-60, 2007.   DOI   ScienceOn
15 Y. Misha, S. Mishar, M. Triphathy, N. Senroy, Z. Y. Dong, “Improving stability of a DFIG-based wind power system with tuned damping controller”, IEEE Trans on Energy Convers, no. 3, vol. 24, pp. 650-60, Sept. 2009.   DOI   ScienceOn
16 F. Hughes, O. Anaya-Lara, N. Jenkins, G. Strbag. “Control of DFIG-based wind generation for power network support,” IEEE Trans. on Power Systems, no. 4, vol. 20, pp. 1958-66, Nov. 2005.   DOI   ScienceOn
17 J.-K. Lyu, J.-H. Heo, M.-K. Kim, J.-K. Park, “Impacts of Wind Power Integration on Generation Dispatch in Power Systems,” J Electr Eng T echnol, vol. 8, no. 3, pp. 453-463, 2013.   DOI   ScienceOn
18 AR. Messina “Inter-area oscillations in power systems: a nonlinear and nonstationary perspective,” Springer, 2009.
19 J. Machowski, J. W. Bailek, J. R. Bumby. “Power system dynamics stability and control,” 2nd edition, Wiley, 2008.
20 W. Yao, L. Jiang, J. Fang, J. Wen, S. Wang, “Damping of Inter-Area Low Frequency Oscillation Using an Adaptive Wide-Area Damping Controller,” J Electr Eng T echnol, vol.9, no. 1, pp. 27-36, 2014.   DOI   ScienceOn