Browse > Article
http://dx.doi.org/10.5370/JEET.2014.9.4.1369

Diagnosis of Medium Voltage Cables for Nuclear Power Plant  

Ha, Che-Wung (APR1400 Licensing Team Advanced Reactors Development Lab. KHNP Central Research Institute)
Lee, Do Hwan (APR1400 Licensing Team Advanced Reactors Development Lab. KHNP Central Research Institute)
Publication Information
Journal of Electrical Engineering and Technology / v.9, no.4, 2014 , pp. 1369-1374 More about this Journal
Abstract
Most accidents of medium-voltage cables installed in nuclear power plants result from the initial defect of internal insulators or the initial failure due to poor construction. However, as the service years of plants increase, the possibility of cable accidents is also rapidly increases. This is primarily caused by electric, mechanical, thermal, and radiation stresses. Recently, much attention is paid to the study of cable diagnoses. To date, partial discharge and Tan${\delta}$ measurements are known as reliable methods to diagnose the aging of medium-voltage cables. High frequency partial discharge measurement techniques have been widely used to diagnose cables in transmission and distribution systems. However, the on-line high frequency partial discharge technique has not been used in the nuclear power plants because of the plant shutdown risk, degraded measurement sensitivity, and application problems. In this paper, the partial discharge measurement with a portable device was tried to evaluate the integrity of the 4.16kV and 13.8kV cable lines. The test results show that the high detection sensitivity can be achieved by the high frequency partial discharge technique. The present technique is highly attractive to diagnose medium voltage cables in nuclear power plants.
Keywords
High frequency partial discharge; Medium voltage cable; Nuclear power plant;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 Plant Support Engineering, "Life Cycle Management Planning Sourcebooks: Medium-Voltage (MV) Cables and Accessories (Terminations and Splices)," EPRI, Palo Alto, November, 2006.
2 Gary Toman, "Aging Management Program Guidance for Medium Voltage Cable Systems for Nuclear Power Plants," Drafet-2, October 14, 2009.
3 Plant Support Engineering, "Aging Management Program Guidance for Medium-Voltage Cable Systems for Nuclear Power Plants," EPRI, Palo Alto, CA, 2010.
4 J. Carey, "Cable Aging Management Program for D.C. Cook Nuclear Plant Units 1 and 2," EPRI, Palo Alto, December, 1996.
5 Su-Kil Lee, et al. "Characteristics of high frequency partial discharge for artificially defected extra high voltage accessories," IEEE conference on Electrical Insulation and Dielectric Phenomena, pp. 682-685, 2000.
6 S. Aggarwal, "Condition Monitoring Program for Electric Cables Used in Nuclear Power Plants," NRC, 2010. 6. vol., 1996. 4.
7 Plant Support Engineering, "Failure Mechanism Assessment of Medium-voltage Ethylene Propylene Rubber Cable-Revision 1", EPRI, Palo Alto, CA: 2009.
8 Dr. Q. Su, "New Techniques for On-line Partical Discharge Measurements," IEEE Xplore, March 08, 2010.
9 Kwang-Jin Lim,"A Study on the Design of a Planar Loop Sensor for Partial Discharge Diagnosis of 22.9 kV XLPE Power Cables," JEET, Vol. 3, No. 4, pp. 559-565, 2008.   과학기술학회마을   DOI   ScienceOn
10 M. Mohana Rao, "Effect of Metallic Particles on E-field Enhancement in Extra High Voltage Gas-insulated Transmission Lines,"JEET, Vol. 5, No. 4, pp. 631-636, 2010.   과학기술학회마을   DOI   ScienceOn