Browse > Article
http://dx.doi.org/10.5370/JEET.2014.9.3.1002

Insulation Design and Reliability Evaluation of ±80kV HVDC XLPE Cables  

Jung, Chae-Kyun (Power Transmission Laboratory, KEPCO Research Institute)
Park, Hung-Sok (Power Transmission Laboratory, KEPCO Research Institute)
Kang, Ji-Won (Power Transmission Laboratory, KEPCO Research Institute)
Publication Information
Journal of Electrical Engineering and Technology / v.9, no.3, 2014 , pp. 1002-1008 More about this Journal
Abstract
This paper describes insulation design and its reliability evaluation of ${\pm}80kV$ HVDC XLPE cable. Recently, the construction of HVDC transmission system, which is combined overhead line with underground cable, has been completed. This system is installed with existing 154 kV AC transmission line on the same tower. In this paper, the lightning transient analysis is firstly reviewed for selection of basic impulse insulation level and nominal insulation thickness. Then the electrical performance tests including load cycle test and superimposed impulse test based on CIGRE TB 496 are performed to evaluate the reliability of newly designed HVDC cable. There is no breakdown for ${\pm}80kV$ HVDC XLPE cable during electrical performance test. Finally, this system is installed in Jeju island based on successful electrical performance test (Type test). After installation tests are also successfully completed.
Keywords
Basic impulse insulation level; HVDC XLPE cable; Lightning; Insulation design; Performance test;
Citations & Related Records
연도 인용수 순위
  • Reference
1 EPRI Technical Report, "AC to DC Power Testing Line Conversion", 2009. 12.
2 C. K. Jung, J. W. Kang, K. Y. Shin, D. H. Kim and D. I. Lee, "Lightning Analysis on HVDC/HVAC Hybrid Transmission System in Korea", 2011 ISH Conference proceedings, 2011.8.
3 C. K. Jung, H. S. Park, J. W. Kang, D. H. Kim, J. W. Shim, B. S. Moon and D. I. Lee, "Basic Impulse Insulation Level Review of ${\pm}80kV$ Nano-composite DC XLPE Cables", CIGRE Colloquium on HVDC and Power Electronic Systems, 2012. 3.
4 Electra 496, "Recommendation for testing DC extruded cable systems for power transmission at a rated voltage up to 500 kV", CIGRE WG B1.32, 2012. 4.
5 IEC 60099-4, "Metal-Oxide Surge Arresters without Gaps for AC Systems", 2009.
6 IEC 60071-1, "Insulation coordination-Part 1: Definition, Principles and rules", 2006. 1.
7 IEC 60071-5, "Insulation coordination-Part 5: Procedures for high-voltage direct current(HVDC)", 2002. 6.
8 Electra 86, Overvoltage on HVDC Cables, CIGRE J/W Group 33/21/14.16, 1994. 8.
9 B. SANDEN, et al., "Recommendations for testing HVDC extruded cable systems for power transmission at a rated voltage up to 500 kV", CIGRE Colloquium on HVDC and Power Electronic Systems, 2012. 3.