Browse > Article
http://dx.doi.org/10.5370/JEET.2013.8.5.1029

Design and Evaluation of a Protection Relay for a Wind Generator Based on the Positive- and Negative-Sequence Fault Components  

Zheng, Taiying (Dept. of Electrical Engineering and Wind energy Grid-Adaptive Technology (WeGAT) Research Centre, Chonbuk National University)
Cha, Seung-Tae (Dept. of Electrical Engineering, Technical University of Denmark)
Kim, Yeon-Hee (Dept. of Electrical Engineering and Wind energy Grid-Adaptive Technology (WeGAT) Research Centre, Chonbuk National University)
Crossley, Peter A. (School of Electrical and Electronic Engineering, University of Manchester)
Lee, Sang Ho (Korea Electrotechnology Research Institute)
Kang, Yong Cheol (Dept. of Electrical Engineering and WeGAT Research Centre, and Smart Grid Research Centre, Chonbuk National University)
Publication Information
Journal of Electrical Engineering and Technology / v.8, no.5, 2013 , pp. 1029-1039 More about this Journal
Abstract
To avoid undesirable disconnection of healthy wind generators (WGs) or a wind power plant, a WG protection relay should discriminate among faults, so that it can operate instantaneously for WG, connected feeder or connection bus faults, it can operate after a delay for inter-tie or grid faults, and it can avoid operating for parallel WG or adjacent feeder faults. A WG protection relay based on the positive- and negative-sequence fault components is proposed in the paper. At stage 1, the proposed relay uses the magnitude of the positive-sequence component in the fault current to distinguish faults requiring non-operation response from those requiring instantaneous or delayed operation responses. At stage 2, the fault type is first determined using the relationships between the positive- and negative-sequence fault components. Then, the relay differentiates between instantaneous operation and delayed operation based on the magnitude of the positive-sequence fault component. Various fault scenarios involving changes in position and type of fault and faulted phases are used to verify the performance of the relay. This paper concludes by implementing the relay on a hardware platform based on a digital signal processor. Results indicate that the relay can successfully distinguish the need for instantaneous, delayed, or non-operation.
Keywords
Wind generator protection; Outage zone minimization; Instantaneous operation; Delayed operation; Non-operation; Symmetrical components;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Steven J Haslam, Peter A Crossley and Nicholas Jenkins, "Design and field testing of a source based protection relay for wind farms," IEEE Trans. on Power Deliv., vol. 14, no. 3, pp. 818-823, Jul. 1999.   DOI   ScienceOn
2 Steven J Haslam, Peter A Crossley and Nicholas Jenkins, "Design and evaluation of a wind farm protection relay," IEE Proc. -Gener. Transm. Distrib., vol. 146, no. 1, pp. 37-44, Jan. 1999.   DOI   ScienceOn
3 Shenghu Li, Shasha Sun and Shaofei Li, "Operation characteristics of zone 3 impedance relays in wind power systems with fixed-speed induction generators," in 2011 Asia-Pacific Power and Energy Engineering Conference, Wuhan, China, Mar. 2011.
4 Schweitzer Engineering Laboratories, SEL-700GW wind generator relay. [online]. Available: http://www. selinc.com/sel-700gw/
5 Taiying Zheng, Yeon-Hee Kim and Yong Cheol Kang, "Protection for a wind turbine generator in a large wind farm," Journal of Electrical Engineering & Technology, vol. 6, no. 4, pp. 466-473, Jul. 2011.   DOI   ScienceOn
6 Taiying Zheng, Seung-Tae Cha, Byung-Eun Lee, Peter A Crossley, Minho Song and Yong Cheol Kang, "Design and evaluation of a protection algorithm for a wind turbine generator based on the fault generated symmetrical components," IEEE PES Innovative Smart Grid Technologies Europe 2011, Manchester, UK, Dec. 2011.
7 Lin Ye and Liang Zhen Lin, "Study of superconducting fault current limiters for system integration of wind farms," IEEE Trans. on Applied Superconductivity, vol. 20, no. 3, pp. 1233-1237, Jun. 2010.   DOI   ScienceOn
8 Eduard Muljadi, Vahan Gevorgian and Francisco Delarosa, "wind power plant enhancement with a fault current limiter," in Proc. 2011 IEEE Power and Energy Society General Meeting, Detroit, MI, USA, Jul. 2011.
9 Wind Plant Collector Design WG, "Wind power plant grounding, overvoltage protection, and insulation coordination," in Proc. 2009 IEEE Power and Energy Society General Meeting, Calgary, Canada, Jul. 2009.
10 Cable News Network (CNN). Clinton hails global warming pact. [Online]. Available: http://www.cnn.com/ALLPOLITICS/1997/12/11/kyoto/
11 Houlei Gao and Peter A Crossley, "Design and evaluation of a directional algorithm for transmission-line protection based on positive-sequence fault components," IEE Proc. -Gener. Transm. Distrib., vol. 153, no. 6, pp. 711-718, Nov. 2006.   DOI   ScienceOn
12 World wind energy report 2010. World wind energy association, Bonn, Germany. [Online]. Available: http://www.wwindea.org
13 The energy report: 100% renewable energy by 2050. World wildlife fund, Washington, DC, USA. [Online]. Available: http://www.worldwildlife.org
14 J. Lewis Blackburn and Thomas J. Domin, Protective relaying principles and applications: 3rd ed., CRC Press, Taylor & Francis Group, LLC, 2007.
15 V. Gevorgian, M. Singh, and E. Muljadi, "Symmetrical and unsymmetrical fault currents of a wind power plant," in 2012 IEEE Power and Energy Society General Meeting, San Diego, California USA, Jul. 22-26, 2012.
16 GE Consumer & Industrial Multilin, W650-Wind generator protection system instruction manuals, 2006 GE Multilin. [online]. Available: http://www.gedigital energy.com/app/ViewFiles.aspx?prod=w650&type=3
17 Michael Reichard, Dale Finney and John Garrity, "Wind farm system protection using peer-to-peer communications," in Proc. IEEE 6th Annu. Conf. Protective Relay Eng., TX, USA, Mar. 2007.