Analysis of Partial Discharge Inception Voltages for the Wrong Positioning Defects in the Joint of Distribution Power Cables  

Kim, Jeong-Tae (Dept. of Electrical and Electronic Engineering, Daejin Univerity)
Kim, Dong-Uk (Dept. of Electrical and Electronic Engineering, Daejin Univerity)
Lee, Young-Jo (Dept. of Electrical and Electronic Engineering, Hanyang Univerity)
Koo, Ja-Yoon (Dept. of Electrical and Electronic Engineering, Hanyang Univerity)
Publication Information
Journal of Electrical Engineering and Technology / v.7, no.6, 2012 , pp. 977-982 More about this Journal
Abstract
In order to find out partial discharge (PD) phenomena in the cable joint due to the poor workmanship during the installation, the relationship between PD inception voltages and joint defects was investigated. For the purpose, in the joint of 22.9kV CNCV cables, electric fields were calculated for various semiconductive layer wrong positioning (WP) defects. And, PDIV were investigated through the experiments and compared with the results of electric field analysis. In all WP defect cases, the PD inception field calculated using measured PDIVs was similarly shown to be the average value of 1.84kV/mm. In addition, the calculated PDIV and the measured PDIV were almost equal, from the PDIV calculation using maximum electric fields and the measured PDIV for the normal case. Throughout this study, it is possible to analyze WP defects due to the poor workmanship and to establish better joint design for the distribution grade extruded cable system.
Keywords
Partial discharge inception voltages; CNCV cable; Joint; Wrong positioning defect; Electric field calculation;
Citations & Related Records

Times Cited By Web Of Science : 0  (Related Records In Web of Science)
연도 인용수 순위
  • Reference
1 C. Aucourt, W. Boone, W. Kalkner, R. D. Naybour, F. Ombello, "Recommendations for a New After laying Test Method for High Voltage Cable Systems", CIGRE 1990 Session, 21-105, 1990
2 Z. Nadolny, J.M. Braun, and R.J. Densley, "Effect Of Mechanical Pressure And Silicone Grease on Partial Discharge Characteristics for Model XLPE Transmission Cable Joint", 11th International Symposium on High Voltage Engineering, 5.297.P5, 1999
3 Z. Nadolny, J.M. Braun, and R.J. Densley, "Influence of Contaminants on Partial Discharge Characteristics for Model XLPE Transmission Cable Joints", 1998 IEEE International Symposium on Electrical Insulation, pp.140-143, 1998
4 E. Kobayashi, F. Komori, Y. Suzuoki, "Partial Discharge Degradation at Insulating Polymer-Polymer Interface", International Symposium on Electrical Insulating Materials, E2-4, pp. 569-572, 1998
5 J. Andersson, S. Gubanski, H. Hillborg, "Properties of Interfaces between Silicone Rubber and Epoxy", IEEE Transactions on Dielectrics and Electrical Insulation Vol. 15, No. 5, pp. 1360-1367, 2008   DOI   ScienceOn
6 M. Nagao, N. Hozumi, K. Kawakami, K. Nagahama, T. Iwasaki, Y. Muramoto, T. Tanaka, "Development of model specimen for evaluating insulation properties and partial discharge phenomena of polymeric solid - solid internal interface", 2003 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, pp.633-636, 2003
7 B. X. Du, L. Gu, "Effects of Interfacial Pressure on Tracking Failure between XLPE and Silicon Rubber", IEEE Transactions on Dielectrics and Electrical Insulation Vol.17, No.6, pp.1922-1930, 2010   DOI   ScienceOn
8 P. Cichecki, E. Gulski, J. J. Smit, R. Jongen, F. Petzold, "Statistical Analysis of Large Amount of Power Cables Diagnostic Data", 2008 International Conference on Condition Monitoring and Diagnosis, Beijing, China, April 21-24, 2008
9 Ja-Yoon Koo, Jeong-Tae Kim, Yun-Ok Cho, Sang- Joon Kim, Il-Keun Song, "An Experimental Investigation of the After Laying Test employable to 22.9 kV CN/CV Power Cables using Oscillating Wave Voltage", The Transactions of Korean Institute of Electrical Engineers, Vol. 47, No. 4, pp. 503-510, 1998 (Korean)