Abstract
Industrial power distribution system includes many kinds of non-linear loads, which produce the harmonics during energy conversion transition. The single-tuned passive filter is widely used to absorb the harmonics and attenuate its undesirable effect in the distribution system. However, the passive filter might be severely stressed, and sometimes even damaged, due to the absorption of harmonics. There is voltage rise on the capacitor when the single-turned harmonic filter is applied. When the capacitor voltage rose above the allowable limit, the expected life of the capacitor will considerably deteriorate. On the other hand, the reactor can experience the spike voltage even if the voltage and current of the capacitor are within the allowable limit, and this accumulated voltage stress of the reactor causes its premature fault. In this paper, we analyzed and compared the harmonic voltage and current of the reactor and capacitor in a single-tuned harmonic filter through the EMTP software and verified them with the experimental results.
Keywords
Harmonics; Reactor; Capacitor; Resonance; Non-linear load;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
Times Cited By Web Of Science : 0  (Related Records In Web of Science)
Times Cited By SCOPUS : 0
연도 인용수 순위
1 Jong-Gyeum Kim et al., “Characteristics Analysis of Capacitor and Reactor for Harmonic Filter”, KIEE, Vol. 58p. No. 1, pp.1-8, Mar., 2009.
2 IEC 60076-6, “Power transformer-part 6: Reactors”.
3 BS EN 60829-1994, “Reactors”.
4 IEEE Standard for Shunt Power Capacitor, IEEE Std 18-2002.
5 Thomas M. Blooming, “Capacitor Application Issues”, IEEE Trans on IAS, Vol. 44, No. 4, pp. 1013- 1026, Jul/Aug. 2008.   DOI   ScienceOn
6 H. W. Dommel, “Electromagnetic Transients Program. Reference Manual (EMTP Theory Book)”, BPA 1986.
7 IEEE Std.1531-2003, “Application and Specification of Harmonic Filters”
8 Konishi Y. “Harmonic compensator-active filter”, Proc of power quality symposium, pp.14-17, 1999. Sep.
9 Douglas Andrews et al., “Harmonic Measurements, Analysis, and Power Factor Correction in a Modern Steel Manufacturing Facility”, IEEE Trans on IAS, Vol. 32, No.3, pp.617-624, May/Jun. 1996   DOI   ScienceOn
10 IEEE Std 519-1992, “IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems”
11 V. Suresh Kumar et al., “Harmonic Mitigation and Power Factor Improvement using Fuzzy Logic and Neutral Network Controlled Active Power Filter”, Journal of Electrical Engineering & Technology, Vol. 3, No. 4, pp.520-527, Dec 2008.   DOI   ScienceOn