Browse > Article
http://dx.doi.org/10.5370/JEET.2010.5.2.220

A Novel Fault Location Scheme on Korean Electric Railway System Using the 9-Conductor Representation  

Lee, Chang-Mu (Korea Railroad Research Institute)
Lee, Han-Sang (Department of Electrical Engineering, Korea University)
Yoon, Dong-Hee (Department of Electrical Engineering, Korea University)
Lee, Han-Min (Korea Railroad Research Institute)
Song, Ji-Young (Department of Electrical Engineering, Korea University)
Jang, Gil-Soo (Department of Electrical Engineering, Korea University)
Han, Byung-Moon (Electrical Engineering, Myongji University)
Publication Information
Journal of Electrical Engineering and Technology / v.5, no.2, 2010 , pp. 220-227 More about this Journal
Abstract
This paper presents a novel fault location scheme on Korean AC electric railway systems. On AC railway system, because of long distance, 40[km] or above, between two railway substations, a fault location technique is very important. Since the fault current flows through the catenary system, it must be modeled exactly to analyze the fault current magnitude and fault location. In this paper, suggesting the novel scheme of fault location, a 9-conductor modeling technique including boost wires and impedance bonds is introduced based on the characteristics of Korean AC electric railway. After obtaining a 9-conductor modeling, the railway system is constructed for computer simulation by using PSCAD/EMTDC. By case studies, we can verify superiority of a new fault location scheme and propose a powerful model for fault analysis on electric railway systems.
Keywords
Fault analysis; Boost wire; Korea AC electric railway system; Fault current ratio;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
Times Cited By SCOPUS : 0
연도 인용수 순위
1 Hanmin Lee, Kwanghae Oh, Changmu Lee, Hyunjune Park, Gilsoo Jang, Saehyuk Kwon, "A Reduced Equivalent Line Constant of the Catenary System," The Transaction of the KIEE, Vol. 53-A, No. 8, pp. 421-431, Aug. 2004   과학기술학회마을
2 B. Yang, Advanced Electric Railway Engineering, vol. 1, Sungandang, Korea, 2003, p. 230, p.319
3 P. Wilson, PSCAD User's Guide, HVDC Research Centre, Canada, 2003
4 Z. Xu, M. Liu, G. Yang, and N. Li, "Application of interval analysis and evidence and evidence theory to fault location," IET Electric Power Applications, Vol. 3, Issue1, pp. 77-84, Jan. 2009   DOI   ScienceOn
5 Chih-Ju Chou, Ying-Tung Hsiao, Jhane-Li Wang, Yaw-Tzong Hwang, "Distribution of earth leakage currents in railway systems with drain autotransformer," IEEE Trans. Power Delivery, Vol. 16, Issue 2, pp. 271-275, Apr. 2001   DOI   ScienceOn
6 Hanmin Lee, Gildong Kim, Sehchan Oh, Gilsoo Jang, Sae-hyuk Kwon, "Fault analysis of Korean AC electric railway system," Electric Power System Research, Vol. 76, Issue 5, pp. 317-326, Mar. 2006   DOI   ScienceOn
7 J. Kim, Power System and Protection Scheme on Electric Railway System, Vol. 1, Kidari, Korea, 2004, p. 262.
8 Hanmin Lee, Kwanghae Oh, Changmu Lee, Sanghoon Chang, Gilsoo Jang, Saehyuk Kwon, "A Reduced Equivalent 5-Conductor Modeling of the Catenary Systme," The Transaction of the KIEE, Vol. 52-A, No. 12, pp. 684-690, Dec. 2003   과학기술학회마을