Browse > Article
http://dx.doi.org/10.5370/JEET.2008.3.4.559

A Study on the Design of a Planar Loop Sensor for Partial Discharge Diagnosis of 22.9 kV XLPE Power Cables  

Lim, Kwang-Jin (Department of Electrical Electronic and Information Engineering, Wonkwang University)
Yang, Sang-Hyun (Department of Electrical Electronic and Information Engineering, Wonkwang University)
Shin, Dong-Hoon (Department of Research & Development Center, PIEZOLAB Co., Ltd.)
Park, Noh-Joon (Department of Electrical Electronic and Information Engineering, Wonkwang University)
Park, Dae-Hee (Department of Electrical Electronic and Information Engineering, Wonkwang University)
Publication Information
Journal of Electrical Engineering and Technology / v.3, no.4, 2008 , pp. 559-565 More about this Journal
Abstract
This study designed a new type of loop antenna that is able to detect partial discharges based on microstrip line technology. In the diagnosis of power cables, partial discharge signals are generally produced at a frequency range less than 100MHz because high frequency PD signals are lost along a propagation path in such cables. The new type of loop antenna sensor has been studied using simulation software known as CST microwave studio version 5.0. In partial discharge measurement experiments, a commercial HFCT sensor was used as a reference sensor. Several experiments were made over HFCT and loop antenna sensors for detecting partial discharges on 22.9kV MV XLPE cable. In this study, we showed the loop antenna designed in this study that can be applied as a commercial HFCT sensor.
Keywords
PD(Partial Discharge); Planar Loop Sensor; Cable Diagnosis; HFCT Sensor;
Citations & Related Records
연도 인용수 순위
  • Reference
1 E. Lemke, H. Elze, W. Weissenberg, 'Experience in PD diagnosis tests of HV cable terminations in service using the ultra-wide band PD probing', XIV Symposium, pp. 221-227, 2003
2 Sander Meijer, Andrea Bovis, Edward Gulski, Johan J. Smit and Alain Girodet', 'Analysis of the Sensitivity of the UHF PD Measuring Technique', Conference Record of the 2000 IEEE International Symposium on Electrical Insulation, Anaheim, CA, USA, pp. 397-399, 2000
3 G.C. Montanari, 'Insulation Diagnosis of High Voltage Apparatus by Partial Discharge Investigation', IEEE 8th International Conference on Properties and Applications of Dielectric Materials, Vol. 1, pp. 1-11, 2006
4 J.Y. Kim, I.K. Song, Y.J. Jung, M.K. Han, Y.J, Sim, J.D. Mun, 'Diagnosis and analysis of the deterioration in underground distribution cables for the criteria of optimum changes', The Korea Institute of Electrical Engineers, Vol. 53C, No. 5, pp. 258-263, 2004
5 Zhiguo Tang, Chengrong Li, Xu Cheng, Wei Wang, Jinzhong Li and Jun Li, 'Partial Discharge Location in Power Transformers Using Wideband RF Detection', IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 13, No. 6, pp. 1193-1199, 2006   DOI   ScienceOn
6 IEEE Std 1434-2000, 'IEEE Trial-Use Guide to the Measurement of Partial Discharges in Rotating Machinery', IEEE Power Engineering Society, pp. 7-8, 2000
7 Y.H. Park, 'A monitoring system for the partial discharges in cables', Open Patents in Korea, 10-2004-0026172, pp. 1-6, 2004
8 Wei Wang, Changyu Li, Chengrong Li, Bin Zheng, Luhua Zhang, 'On Site PD Detection on XLPE Cable Accessories', IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 12, No. 2, pp. 216-222, 2005   DOI   ScienceOn